New ADAAG | DOJ Standards for Accessible Design | International Building Code |
---|---|---|
CHAPTER 8: SPECIAL ROOMS, SPACES, AND ELEMENTS |
ANSI Chapter 8. Special Rooms and Spaces |
|
801 General |
ANSI 801 General |
|
801.1 Scope.The provisions of Chapter 8 shall apply where required by Chapter 2 or where referenced by a requirement in this document. |
ANSI 801.1 Scope. Special rooms and spaces required to be accessible by the scoping provisions adopted by the administrative authority shall comply with the applicable provisions of Chapter 8. |
|
802 Wheelchair Spaces, Companion Seats, and Designated Aisle Seats |
4.33 Assembly Areas. |
ANSI 802 Assembly Areas |
802.1 Wheelchair Spaces. Wheelchair spaces shall comply with 802.1. |
4.33.1 Minimum Number. Assembly and associated areas required to be accessible by 4.1 shall comply with 4.33. |
ANSI 802.1 General. Wheelchair spaces and wheel chair space locations in assembly areas with spectator seating shall comply with Section 802. |
802.1.1 Floor or Ground Surface. The floor or ground surface of wheelchair spaces shall comply with 302. Changes in level are not permitted. EXCEPTION: Slopes not steeper than 1:48 shall be permitted. |
4.33.4 Surfaces. The ground or floor at wheelchair locations shall be level and shall comply with 4.5. |
ANSI 802.2 Floor Surfaces. The floor surface of wheelchair space locations shall have a slope not steeper than 1:48 and shall comply with Section 302. |
802.1.2 Width. A single wheelchair space shall be 36 inches (915 mm) wide minimum Where two adjacent wheelchair spaces are provided, each wheelchair space shall be 33 inches (840 mm) wide minimum. |
4.33.2 Size of Wheelchair Locations. Each wheelchair location shall provide minimum clear ground or floor spaces as shown in Fig. 46. NOTE:Figure 46(a) indicates that if seating space for two wheelchair users is accessed from the front or rear, the minimum space required is 48 inches (1220 mm) deep by 66 inches (1675 mm) wide. Figure 46(b) indicates that if seating space for two wheelchair users is accessed from the side, the minimum space required is 60 inches (1525 mm) deep by 66 inches (1675 mm) wide. |
ANSI 802.3 Width. A single wheelchair space shall be 36 inches (915 mm) minimum in width. Where two adjacent wheelchair spaces are provided, each wheelchair space shall be 33 inches (840 mm) minimum in width. |
802.1.3 Depth. Where a wheelchair space can be entered from the front or rear, the wheelchair space shall be 48 inches (1220 mm) deep minimum. Where a wheelchair space can be entered only from the side, the wheelchair space shall be 60 inches (1525 mm) deep minimum. |
ANSI 802.4 Depth. Where a wheelchair space location can be entered from the front or rear, the wheelchair space shall be 48 inches (1220 mm) minimum in depth. Where a wheelchair space location can only be entered from the side, the wheelchair space shall be 60 inches (1525 mm) minimum in depth. |
|
802.1.4 Approach. Wheelchair spaces shall adjoin accessible routes. Accessible routes shall not overlap wheelchair spaces. |
ANSI 802.5 Approach. The wheelchair space location shall adjoin an accessible route. The accessible route shall not overlap the wheelchair space location. |
|
802.1.5 Overlap. Wheelchair spaces shall not overlap circulation paths. |
4.33.3 Placement of Wheelchair Locations. Wheelchair areas shall be an integral part of any fixed seating plan and shall be provided so as to provide people with physical disabilities a choice of admission prices and lines of sight comparable to those for members of the general public. They shall adjoin an accessible route that also serves as a means of egress in case of emergency. At least one companion fixed seat shall be provided next to each wheelchair seating area. When the seating capacity exceeds 300, wheelchair spaces shall be provided in more than one location. Readily removable seats may be installed in wheelchair spaces when the spaces are not required to accommodate wheelchair users. EXCEPTION: Accessible viewing positions may be clustered for bleachers, balconies, and other areas having sight lines that require slopes of greater than 5 percent. Equivalent accessible viewing positions may be located on levels having accessible egress. |
ANSI 802.5.1 Overlap. A wheelchair space location shall not overlap the required width of an aisle. |
802.2 Lines of Sight. Lines of sight to the screen, performance area, or playing field for spectators in wheelchair spaces shall comply with 802.2. |
ANSI 802.9 Lines of Sight. Where spectators are expected to remain seated for purposes of viewing events, spectators in wheelchair space locations shall be provided with a line of sight in accordance with Section 802.9.1. Where spectators in front of the wheelchair space locations will be expected to stand at their seats for purposes of viewing events, spectators in wheelchair space locations shall be provided with a line of sight in accordance with Section 802.9.2. |
|
802.2.1 Lines of Sight Over Seated Spectators. Where spectators are expected to remain seated during events, spectators in wheelchair spaces shall be afforded lines of sight complying with 802.2.1. |
ANSI 802.9.1 Line of Sight over Seated Spectators. Where spectators are expected to remain seated during events, spectators seated in wheelchair space locations shall be provided with lines of sight to the performance area or playing field comparable to that provided to spectators in closest proximity to the wheelchair space location. Where seating provides lines of sight over heads, spectators in wheelchair space locations shall be afforded lines of sight complying with Section 802.9.1.1. Where wheelchair space locations provide lines of sight over the shoulder and between heads, spectators in wheelchair space locations shall be afforded lines of sight complying with Section 802.9.1.2. |
|
802.2.1.1 Lines of Sight Over Heads. Where spectators are provided lines of sight over the heads of spectators seated in the first row in front of their seats, spectators seated in wheelchair spaces shall be afforded lines of sight over the heads of seated spectators in the first row in front of wheelchair spaces. |
ANSI 802.9.1.1 Lines of Sight over Heads. Spectators seated in wheelchair space locations shall be afforded lines of sight over the heads of seated individuals in the first row in front of the wheelchair space location. |
|
802.2.1.2 Lines of Sight Between Heads. Where spectators are provided lines of sight over the shoulders and between the heads of spectators seated in the first row in front of their seats, spectators seated in wheelchair spaces shall be afforded lines of sight over the shoulders and between the heads of seated spectators in the first row in front of wheelchair spaces. |
ANSI 802.9.1.2 Lines of Sight between Heads. Spectators seated in wheelchair space locations shall be afforded lines of sight over the shoulders and between the heads of seated individuals in the first row in front of the wheelchair space location. |
|
802.2.2 Lines of Sight Over Standing Spectators. Where spectators are expected to stand during events, spectators in wheelchair spaces shall be afforded lines of sight complying with 802.2.2. |
ANSI 802.9.2 Line of Sight over Standing Spectators. Wheelchair space locations required to provide a line of sight over standing spectators shall comply with Section 802.9.2. |
|
ANSI 802.9.2.1 Distance from Adjacent Seating. The front of the wheelchair space location shall be 12 inches (305 mm) maximum from the back of the chair or bench in front. |
||
802.2.2.1 Lines of Sight Over Heads. Where standing spectators are provided lines of sight over the heads of spectators standing in the first row in front of their seats, spectators seated in wheelchair spaces shall be afforded lines of sight over the heads of standing spectators in the first row in front of wheelchair spaces. |
ANSI 802.9.2.2 Elevation. The elevation of the tread on which a wheelchair space location is located shall comply with Table 802.9.2.2. For riser heights other than those provided, interpolations shall be permitted. |
|
802.2.2.2 Lines of Sight Between Heads. Where standing spectators are provided lines of sight over the shoulders and between the heads of spectators standing in the first row in front of their seats, spectators seated in wheelchair spaces shall be afforded lines of sight over the shoulders and between the heads of standing spectators in the first row in front of wheelchair spaces. |
Riser height | Minimum height of the wheelchair space location based on row spacing1 | ||
---|---|---|---|
Rows less than 33 inches (840 mm)2 | Rows 33 inches (840 mm) to 44 inches (1120 mm)2 | Rows over 44 inches (1120 mm)2 | |
(continued) | |||
1The height of the wheelchair space location is the vertical distance from the tread of the row of seats directly in front of the wheelchair space location to the tread of the wheelchair space location. 2The row spacing is the back–to–back horizontal distance between the rows of seats in front of the wheelchair space location. 3Seating treads less than 33 inches (840 mm) in depth are not permitted with risers greater than 18 inches (455 mm) in height. 4Seating treads less than 44 inches (1120 mm) in depth are not permitted with risers greater than 27 inches (685 mm) in height. NOTE: Table 802.8.9 is based on providing a spectator in a wheelchair a line of sight over the head of a spectator two rows in front of the wheelchair space location using average anthropometrical data. The table is based on the following calculation: [(2X+34)(Y–2.25)/X]+(20.2–Y) where Y is the riser height of the rows in front of the wheelchair space location and X is the tread depth of the rows in front of the wheelchair space location. The calculation is based on the front of the wheelchair space location being located 12 inches (305 mm) from the back of the seating tread directly in front and the eye of the standing spectator being set back 8 inches (205 mm) from the riser. |
|||
0 inch (0 mm) |
16 inch (405 mm) |
16 inch (405 mm) |
16 inch (405 mm) |
4 inch (102 mm) |
22 inch (560 mm) |
21 inch (535 mm) |
21 inch (535 mm) |
8 inch (205 mm) |
31 inch (785 mm) |
30 inch (760 mm) |
28 inch (710 mm) |
12 inch (305 mm) |
40 inch (1015 mm) |
37 inch (940 mm) |
35 inch (890 mm) |
16 inch (406 mm) |
49 inch (1245 mm) |
45 inch (1145 mm) |
42 inch (1065 mm) |
20 inch (510 mm)3 |
58 inch (1475 mm) |
53 inch (1345 mm) |
49 inch (1245 mm) |
24 inch (610 mm) |
N/A |
61 inch (1550 mm) |
56 inch (1420 mm) |
28 inch (710 mm)4 |
N/A |
69 inch (1750 mm) |
63 inch (1600 mm) |
32 inch (815 mm) |
N/A |
N/A |
70 inch (1780 mm) |
36 inch (915 mm) and higher |
N/A |
N/A |
77 inch (1955 mm) |
New ADAAG | DOJ Standards for Accessible Design | International Building Code |
---|---|---|
802.3.1 Alignment. In row seating, companion seats shall be located to provide shoulder alignment with adjacent wheelchair spaces. The shoulder alignment point of the wheelchair space shall be measured 36 inches (915 mm) from the front of the wheelchair space. The floor surface of the companion seat shall be at the same elevation as the floor surface of the wheelchair space. |
ANSI 802.7.2 Companion Seat Alignment. In row seating, the companion seat shall be located to provide shoulder alignment with the wheelchair space occupant. The shoulder of the wheelchair space occupant is considered to be 36 inches (915 mm) from the front of the wheelchair space. The floor surface for the companion seat shall be at the same elevation as the wheelchair space floor surface. |
|
802.3.2 Type. Companion seats shall be equivalent in size, quality, comfort, and amenities to the seating in the immediate area. Companion seats shall be permitted to be movable. |
ANSI 802.7.1 Companion Seat Type. The companion seat shall be comparable in size and quality to assure equivalent comfort to the seats within the seating area adjacent to the wheelchair space location. Companion seats shall be permitted to be moveable. |
|
802.4 Designated Aisle Seats. Designated aisle seats shall comply with 802.4. |
ANSI 802.8 Designated Aisle Seats. Designated aisle seats shall comply with Section 802.8. |
|
802.4.1 Armrests. Where armrests are provided on the seating in the immediate area, folding or retractable armrests shall be provided on the aisle side of the seat. |
ANSI 802.8.1 Armrests. Where armrests are provided on seating in the immediate area of designated aisle seats, folding or retractable armrests shall be provided on the aisle side of the designated aisle seat. |
|
802.4.2 Identification. Each designated aisle seat shall be identified by a sign or marker. |
4.1.3(19)(a) …. In addition, one percent, but not less than one, of all fixed seats shall be aisle seats with no armrests on the aisle side, or removable or folding armrests on the aisle side. Each such seat shall be identified by a sign or marker. Signage notifying patrons of the availability of such seats shall be posted at the ticket office. Aisle seats are not required to comply with 4.33.4. |
ANSI 802.8.2 Identification. Each designated aisle seat shall be identified by a sign or marker. |
803 Dressing, Fitting, and Locker Rooms |
4.35 Dressing, Fitting, and Locker Rooms. |
ANSI 803 Dressing, Fitting, and Locker Rooms |
803.1 General. Dressing, fitting, and locker rooms shall comply with 803. |
4.35.1 General. Dressing, fitting, and locker rooms required to be accessible by 4.1 shall comply with 4.35 and shall be on an accessible route. |
ANSI 803.1 General. Accessible dressing, fitting, and locker rooms shall comply with Section 803. |
803.2 Turning Space. Turning space complying with 304 shall be provided within the room. |
4.35.2 Clear Floor Space. A clear floor space allowing a person using a wheelchair to make a 180-degree turn shall be provided in every accessible dressing room entered through a swinging or sliding door. No door shall swing into any part of the turning space. Turning space shall not be required in a private dressing room entered through a curtained opening at least 32 in (815 mm) wide if clear floor space complying with section 4.2 renders the dressing room usable by a person using a wheelchair. |
ANSI 803.2 Turning Space. A turning space complying with Section 304 shall be provided within the room. |
803.3 Door Swing. Doors shall not swing into the room unless a clear floor or ground space complying with 305.3 is provided beyond the arc of the door swing. |
4.35.3 Doors. All doors to accessible dressing rooms shall be in compliance with section 4.13. |
ANSI 803.3 Door Swing. Doors shall not swing into the room unless a clear floor space complying with Section 305.3 is provided within the room, beyond the arc of the door swing. |
803.4 Benches. A bench complying with 903 shall be provided within the room. |
4.35.4 Bench. Every accessible dressing room shall have a 24 in by 28 in (610 mm by 1220 mm) bench fixed to the wall along the longer dimension. The bench shall be mounted 17 in to 19 in (430 mm to 485 mm) above the finish floor. Clear floor space shall be provided alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. The structural strength of the bench and attachments shall comply with 4.26.3. Where installed in conjunction with showers, swimming pools, or other wet locations, water shall not accumulate upon the surface of the bench and the bench shall have a slip-resistant surface. See also Appendix 4.35.4. |
ANSI 803.4 Benches. A bench complying with Section 903 shall be provided within the room. |
803.5 Coat Hooks and Shelves. Coat hooks provided within the room shall be located within one of the reach ranges specified in 308. Shelves shall be 40 inches (1015 mm) minimum and 48 inches (1220 mm) maximum above the finish floor or ground. |
ANSI 803.5 Coat Hooks and Shelves. Accessible coat hooks provided within the room shall accommodate a forward reach or side reach complying with Section 308. Where provided, a shelf shall be 40 inches (1015 mm) minimum and 48 inches (1220 mm) maximum above the floor. |
|
4.35.5 Mirror. Where mirrors are provided in dressing rooms of the same use, then in an accessible dressing room, a full-length mirror, measuring at least 18 in wide by 54 in high (460 mm by 1370 mm), shall be mounted in a position affording a view to a person on the bench as well as to a person in a standing position. |
||
804 Kitchens and Kitchenettes |
ANSI 804 Kitchens and Kitchenettes |
|
804.1 General. Kitchens and kitchenettes shall comply with 804. |
ANSI 804.1 General. Accessible kitchens and kitchenettes shall comply with Section 804. |
|
804.2 Clearance. Where a pass through kitchen is provided, clearances shall comply with 804.2.1. Where a U-shaped kitchen is provided, clearances shall comply with 804.2.2. EXCEPTION: Spaces that do not provide a cooktop or conventional range shall not be required to comply with 804.2. |
ANSI 804.2 Clearance. Where a pass–through kitchen is provided, clearances shall comply with Section 804.2.1. Where a U–shaped kitchen is provided, clearances shall comply with Section 804.2.2. EXCEPTION: Spaces that do not provide a cooktop or conventional range shall not be required to comply with Section 804.2. |
|
804.2.1 Pass Through Kitchen. In pass through kitchens where counters, appliances or cabinets are on two opposing sides, or where counters, appliances or cabinets are opposite a parallel wall, clearance between all opposing base cabinets, counter tops, appliances, or walls within kitchen work areas shall be 40 inches (1015 mm) minimum. Pass through kitchens shall have two entries. |
ANSI 804.2.1 Pass–through Kitchens. In pass–through kitchens where counters, appliances or cabinets are on two opposing sides, or where counters, appliances or cabinets are opposite a parallel wall, clearance between all opposing base cabinets, counter tops, appliances, or walls within kitchen work areas shall be 40 inches (1015 mm) minimum. Pass–through kitchens shall have two entries. |
|
804.2.2 U-Shaped. In U-shaped kitchens enclosed on three contiguous sides, clearance between all opposing base cabinets, counter tops, appliances, or walls within kitchen work areas shall be 60 inches (1525 mm) minimum. |
ANSI 804.2.2 U–Shaped Areas. In kitchens enclosed on three contiguous sides, clearance between all opposing base cabinets, countertops, appliances, or walls within kitchen work areas shall be 60 inches (1525 mm) minimum. |
|
804.3 Kitchen Work Surface. In residential dwelling units required to comply with 809, at least one 30 inches (760 mm) wide minimum section of counter shall provide a kitchen work surface that complies with 804.3. |
||
804.3.1 Clear Floor or Ground Space. A clear floor space complying with 305 positioned for a forward approach shall be provided. The clear floor or ground space shall be centered on the kitchen work surface and shall provide knee and toe clearance complying with 306. EXCEPTION: Cabinetry shall be permitted under the kitchen work surface provided that all of the following conditions are met: (a) the cabinetry can be removed without removal or replacement of the kitchen work surface; (b) the finish floor extends under the cabinetry; and (c) the walls behind and surrounding the cabinetry are finished. |
||
804.3.2 Height. The kitchen work surface shall be 34 inches (865 mm) maximum above the finish floor or ground. EXCEPTION: A counter that is adjustable to provide a kitchen work surface at variable heights, 29 inches (735 mm) minimum and 36 inches (915 mm) maximum, shall be permitted. |
ANSI 804.3 Work Surface. Work surfaces shall comply with Section 902. EXCEPTION: Spaces that do not provide a cooktop or conventional range shall not be required to provide an accessible work surface. |
|
804.3.3 Exposed Surfaces. There shall be no sharp or abrasive surfaces under the work surface counters. |
||
804.4 Sinks. Sinks shall comply with 606. |
ANSI 804.4 Sinks. Sinks shall comply with Section 606. |
|
804.5 Storage. At least 50 percent of shelf space in storage facilities shall comply with 811. |
ANSI 804.5 Storage. At least 50 percent of shelf space in cabinets shall comply with Section 905. |
|
804.6 Appliances. Where provided, kitchen appliances shall comply with 804.6. |
ANSI 804.6 Appliances. Where provided, kitchen appliances shall comply with Section 804.6. |
|
804.6.1 Clear Floor or Ground Space. A clear floor or ground space complying with 305 shall be provided at each kitchen appliance. Clear floor or ground spaces shall be permitted to overlap. |
ANSI 804.6.1 Clear Floor Space. A clear floor space complying with Section 305 shall be provided at each kitchen appliance. Clear floor spaces are permitted to overlap. |
|
804.6.2 Operable Parts. All appliance controls shall comply with 309. EXCEPTIONS: 1. Appliance doors and door latching devices shall not be required to comply with 309.4. 2. Bottom-hinged appliance doors, when in the open position, shall not be required to comply with 309.3. |
ANSI 804.6.2 Operable Parts. All appliance controls shall comply with Section 309. EXCEPTIONS: 1. Appliance doors and door latching devices shall not be required to comply with Section 309.4. 2. Bottom–hinged appliance doors, when in the open position, shall not be required to comply with Section 309.3. |
|
804.6.3 Dishwasher. Clear floor or ground space shall be positioned adjacent to the dishwasher door. The dishwasher door, in the open position, shall not obstruct the clear floor or ground space for the dishwasher or the sink. |
ANSI 804.6.3 Dishwasher. A clear floor space, positioned adjacent to the dishwasher door, shall be provided. The dishwasher door in the open position shall not obstruct the clear floor space for the dishwasher or an adjacent sink. |
|
804.6.4 Range or Cooktop. Where a forward approach is provided, the clear floor or ground space shall provide knee and toe clearance complying with 306. Where knee and toe space is provided, the underside of the range or cooktop shall be insulated or otherwise configured to prevent burns, abrasions, or electrical shock. The location of controls shall not require reaching across burners. |
ANSI 804.6.4 Range or Cooktop. A clear floor space, positioned for a parallel or forward approach to the space for a range or cooktop, shall be provided. Where the clear floor space is positioned for a forward approach, knee and toe clearance complying with Section 306 shall be provided. Where knee and toe space is provided, the underside of the range or cooktop shall be insulated or otherwise configured to prevent burns, abrasions, or electrical shock. The location of controls shall not require reaching across burners. |
|
804.6.5 Oven. Ovens shall comply with 804.6.5. |
ANSI 804.6.5 Oven. Ovens shall comply with Section 804.6.5. |
|
804.6.5.1 Side-Hinged Door Ovens. Side-hinged door ovens shall have the work surface required by 804.3 positioned adjacent to the latch side of the oven door. |
ANSI 804.6.5.1 Side–Hinged Door Ovens. Side–hinged door ovens shall have a work surface complying with Section 804.3 positioned adjacent to the latch side of the oven door. |
|
804.6.5.2 Bottom-Hinged Door Ovens. Bottom-hinged door ovens shall have the work surface required by 804.3 positioned adjacent to one side of the door. |
ANSI 804.6.5.2 Bottom–Hinged Door Ovens. Bottom–hinged door ovens shall have a work surface complying with Section 804.3 positioned adjacent to one side of the door. |
|
804.6.5.3 Controls. Ovens shall have controls on front panels. |
ANSI 804.6.5.3 Controls. Ovens shall have controls on front panels. |
|
804.6.6 Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer space 54 inches (1370 mm) maximum above the finish floor or ground. The clear floor or ground space shall be positioned for a parallel approach to the space dedicated to a refrigerator/freezer with the centerline of the clear floor or ground space offset 24 inches (610 mm) maximum from the centerline of the dedicated space. |
ANSI 804.6.6 Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches (1370 mm) maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches (610 mm) maximum from the centerline of the dedicated space. |
|
805 Medical Care and Long-Term Care Facilities |
6. MEDICAL CARE FACILITIES. |
|
805.1 General. Medical care facility and long-term care facility patient or resident sleeping rooms required to provide mobility features shall comply with 805. |
6.3 Patient Bedrooms. Provide accessible patient bedrooms in compliance with section 4. Accessible patient bedrooms shall comply with the following: |
|
805.2 Turning Space. Turning space complying with 304 shall be provided within the room. |
(2) Each bedroom shall have adequate space to provide a maneuvering space that complies with 4.2.3. In rooms with two beds, it is preferable that this space be located between beds. |
|
805.3 Clear Floor or Ground Space. A clear floor space complying with 305 shall be provided on each side of the bed. The clear floor space shall be positioned for parallel approach to the side of the bed. |
(3) Each bedroom shall have adequate space to provide a minimum clear floor space of 36 in (915 mm) along each side of the bed and to provide an accessible route complying with 4.3.3 to each side of each bed. |
|
805.4 Toilet and Bathing Rooms. Toilet and bathing rooms that are provided as part of a patient or resident sleeping room shall comply with 603. Where provided, no fewer than one water closet, one lavatory, and one bathtub or shower shall comply with the applicable requirements of 603 through 610. |
6.4 Patient Toilet Rooms. Where toilet/bathrooms are provided as a part of a patient bedroom, each patient bedroom that is required to be accessible shall have an accessible toilet/bathroom that complies with 4.22 or 4.23 and shall be on an accessible route. |
|
806 Transient Lodging Guest Rooms |
9.2 Requirements for Accessible Units, Sleeping Rooms and Suites. |
ANSI 1002 Accessible Units |
806.1 General. Transient lodging guest rooms shall comply with 806. Guest rooms required to provide mobility features shall comply with 806.2. Guest rooms required to provide communication features shall comply with 806.3. |
||
806.2 Guest Rooms with Mobility Features. Guest rooms required to provide mobility features shall comply with 806.2. |
9.2.1 General. Units, sleeping rooms, and suites required to be accessible by 9.1 shall comply with 9.2. |
ANSI 1002.1 General. Accessible units shall comply with Section 1002. |
4.3.2(4) An accessible route shall connect at least one accessible entrance of each accessible dwelling unit with those exterior and interior spaces and facilities that serve the accessible dwelling unit. |
ANSI 1002.2 Primary Entrance. The accessible primary entrance shall be on an accessible route from public and common areas. The primary entrance shall not be to a bedroom. |
|
9.2.2 Minimum Requirements. An accessible unit, sleeping room or suite shall be on an accessible route complying with 4.3 and have the following accessible elements and spaces. |
||
ANSI 1002.3 Accessible Route. Accessible routes within Accessible units shall comply with Section 1002.3. Exterior spaces less than 30 inches (760 mm) in depth or width shall comply with Sections 1002.3.1, 1002.3.3, 302, and 303. |
||
9.2.2(2) An accessible route complying with 4.3 shall connect all accessible spaces and elements, including telephones, within the unit, sleeping room, or suite. This is not intended to require an elevator in multi-story units as long as the spaces identified in 9.2.2(6) and (7) are on accessible levels and the accessible sleeping area is suitable for dual occupancy. |
ANSI 1002.3.1 Location. At least one accessible route shall connect all spaces and elements that are a part of the unit. Where only one accessible route is provided, it shall not pass through bathrooms and toilet rooms, closets, or similar spaces. EXCEPTION: An accessible route is not required to unfinished attics and unfinished basements that are part of the unit. |
|
806.2.1 Living and Dining Areas. Living and dining areas shall be accessible. |
9.2.2(6)Where provided as part of an accessible unit, sleeping room, or suite, the following spaces shall be accessible and shall be on an accessible route: (a) the living area. |
|
(b) the dining area. |
||
806.2.2 Exterior Spaces. Exterior spaces, including patios, terraces and balconies that serve the guest room shall be accessible. |
(d) patios, terraces, or balconies. EXCEPTION: The requirements of 4.13.8 and 4.3.8 do not apply where it is necessary to utilize a higher door threshold or a change in level to protect the integrity of the unit from wind/water damage. Where this exception results in patios, terraces or balconies that are not at an accessible level, equivalent facilitation shall be provided (e.g., equivalent facilitation at a hotel patio or balcony might consist of providing raised decking or a ramp to provide accessibility). |
|
ANSI 1002.3.3 Components. Accessible routes shall consist of one or more of the following elements: walking surfaces with a slope not steeper than 1:20, ramps, elevators, and platform lifts. |
||
1002.4 Walking Surfaces. Walking surfaces that are part of an accessible route shall comply with Section 403. |
||
9.2.2(3) Doors and doorways designed to allow passage into and within all sleeping rooms, suites or other covered units shall comply with 4.13. |
ANSI 1002.5 Doors and Doorways. The primary entrance door to the unit, and all other doorways intended for user passage, shall comply with Section 404. EXCEPTION: Existing doors to hospital patient sleeping rooms shall be exempt from the requirement for space at the latch side provided the door is 44 inches (1120 mm) minimum in width. |
|
ANSI 1002.6 Ramps. Ramps shall comply with Section 405. |
||
ANSI 1002.7 Elevators. Elevators within the unit shall comply with Section 407, 408, or 409. |
||
ANSI 1002.8 Platform Lifts. Platform lifts within the unit shall comply with Section 410. |
||
9.2.2(5) All controls in accessible units, sleeping rooms, and suites shall comply with 4.27. |
ANSI 1002.9 Operable Parts. Lighting controls, electrical switches and receptacle outlets, environmental controls, appliance controls, operating hardware for operable windows, plumbing fixture controls, and user controls for security or intercom systems shall comply with Section 309. EXCEPTIONS: 1. Receptacle outlets serving a dedicated use. 2. One receptacle outlet shall not be required to comply with Section 309 where all of the following conditions are met: (a) the receptacle outlet is above a length of countertop that is uninterrupted by a sink or appliance; (b) at least one receptacle outlet complying with Section 1002.9 is provided for that length of countertop; and (c) all other receptacle outlets provided for that length of countertop comply with Section 1002.9. 3. Floor receptacle outlets. 4. HVAC diffusers. 5. Controls mounted on ceiling fans. 6. Where redundant controls other than light switches are provided for a single element, one control in each space shall not be required to be accessible. |
|
9.2.2(6)(c) at least one sleeping area. |
||
806.2.3 Sleeping Areas. At least one sleeping area shall provide a clear floor space complying with 305 on both sides of a bed. The clear floor space shall be positioned for parallel approach to the side of the bed. EXCEPTION: Where a single clear floor space complying with 305 positioned for parallel approach is provided between two beds, a clear floor or ground space shall not be required on both sides of a bed. |
9.2.2(1) Accessible sleeping rooms shall have a 36 in (915 mm) clear width maneuvering space located along both sides of a bed, except that where two beds are provided, this requirement can be met by providing a 36 in (915 mm) wide maneuvering space located between the two beds. |
IBC E104.1 General. Transient lodging facilities shall be provided with accessible features in accordance with Sections E104.2 and E104.3. Group I-3 occupancies shall be provided with accessible features in accordance with Sections E104.3 and E104.4. |
IBC E104.2 Accessible beds. In rooms or spaces having more than 25 beds, five percent of the beds shall have a clear floor space complying with ICC A117.1. |
||
IBC E104.2.1 Sleeping areas. A clear floor space complying with ICC A117.1 shall be provided on both sides of the accessible bed. The clear floor space shall be positioned for parallel approach to the side of the bed. Exception: This requirement shall not apply where a single clear floor space complying with ICC A117.1 positioned for parallel approach is provided between two beds. |
||
806.2.4 Toilet and Bathing Facilities. At least one bathroom that is provided as part of a guest room shall comply with 603. No fewer than one water closet, one lavatory, and one bathtub or shower shall comply with 603 through 610. In addition, required roll-in shower compartments shall comply with 608.2.2 or 608.2.3. Toilet and bathing fixtures required to comply with 603 through 610 shall be permitted to be located in more than one toilet or bathing area, provided that travel between fixtures does not require travel between other parts of the guest room. |
9.2.2(6) (e) at least one full bathroom (i.e., one with a water closet, a lavatory, and a bathtub or shower). (f) if only half baths are provided, at least one half bath. |
ANSI 1002.11 Toilet and Bathing Facilities. Toilet and bathing facilities shall comply with Sections 603 through 610. |
806.2.4.1 Vanity Counter Top Space. If vanity counter top space is provided in non-accessible guest toilet or bathing rooms, comparable vanity counter top space, in terms of size and proximity to the lavatory, shall also be provided in accessible guest toilet or bathing rooms. |
ANSI 1002.11.1 Vanity Counter Top Space. If vanity counter top space is provided in nonaccessible dwelling or sleeping units within the same facility, equivalent vanity counter top space, in terms of size and proximity to the lavatory, shall also be provided in Accessible units. |
|
806.2.5 Kitchens and Kitchenettes. Kitchens and kitchenettes shall comply with 804. |
9.2.2(7) Kitchens, Kitchenettes, or Wet Bars. When provided as accessory to a sleeping room or suite, kitchens, kitchenettes, wet bars, or similar amenities shall be accessible. Clear floor space for a front or parallel approach to cabinets, counters, sinks, and appliances shall be provided to comply with 4.2.4. Countertops and sinks shall be mounted at a maximum height of 34 in (865 mm) above the floor. At least fifty percent of shelf space in cabinets or refrigerator/freezers shall be within the reach ranges of 4.2.5 or 4.2.6 and space shall be designed to allow for the operation of cabinet and/or appliance doors so that all cabinets and appliances are accessible and usable. Controls and operating mechanisms shall comply with 4.27. |
ANSI 1002.12 Kitchens. Kitchens shall comply with Section 804. At least one work surface, 30 inches (760 mm) minimum in length, shall comply with Section 902. |
806.2.6 Turning Space. Turning space complying with 304 shall be provided within the guest room. |
ANSI 1002.3.2 Turning Space. All rooms served by an accessible route shall provide a turning space complying with Section 304. |
|
ANSI 1002.10 Laundry Equipment. Washing machines and clothes dryers shall comply with Section 611. |
||
ANSI 1002.13 Windows. Where operable windows are provided, at least one window in each sleeping, living, or dining space shall have operable parts complying with Section 1002.9. Each required operable window shall have operable parts complying with Section 1002.9. |
||
9.2.2(4) If fixed or built-in storage facilities such as cabinets, shelves, closets, and drawers are provided in accessible spaces, at least one of each type provided shall contain storage space complying with 4.25. Additional storage may be provided outside of the dimensions required by 4.25. |
ANSI 1002.14 Storage Facilities. Where storage facilities are provided, they shall comply with Section 905. Kitchen cabinets shall comply with Section 804.5. |
|
806.3 Guest Rooms with Communication Features. Guest rooms required to provide communication features shall comply with 806.3. |
9.3 Visual Alarms, Notification Devices and Telephones. |
IBC E104.3 Communication features. Communication features complying with ICC A117.1 shall be provided in accordance with Sections E104.3.1 through E104.3.4. |
806.3.1 Alarms. Where emergency warning systems are provided, alarms complying with 702 shall be provided. |
9.3.1 General. In sleeping rooms required to comply with this section, auxiliary visual alarms shall be provided and shall comply with 4.28.4. Visual notification devices shall also be provided in units, sleeping rooms and suites to alert room occupants of incoming telephone calls and a door knock or bell. Notification devices shall not be connected to auxiliary visual alarm signal appliances. Permanently installed telephones shall have volume controls complying with 4.31.5; an accessible electrical outlet within 4 ft (1220 mm) of a telephone connection shall be provided to facilitate the use of a text telephone. |
IBC 907.9.1.3 Groups I-1 and R-1. Group I-1 and R-1 sleeping units in accordance with Table 907.9.1.3 shall be provided with a visible alarm notification appliance, activated by both the in‑room smoke alarm and the building fire alarm system. |
806.3.2 Notification Devices. Visible notification devices shall be provided to alert room occupants of incoming telephone calls and a door knock or bell. Notification devices shall not be connected to visible alarm signal appliances. Telephones shall have volume controls compatible with the telephone system and shall comply with 704.3. Telephones shall be served by an electrical outlet complying with 309 located within 48 inches (1220 mm) of the telephone to facilitate the use of a TTY. |
IBC E104.3.4 Notification devices. Visual notification devices shall be provided to alert room occupants of incoming telephone calls and a door knock or bell. Notification devices shall not be connected to visual alarm signal appliances. Permanently installed telephones shall have volume controls and an electrical outlet complying with ICC A117.1 located within 48 inches (1219 mm) of the telephone to facilitate the use of a TTY. |
|
9.3.2 Equivalent Facilitation. For purposes of this section, equivalent facilitation shall include the installation of electrical outlets (including outlets connected to a facility's central alarm system) and telephone wiring in sleeping rooms and suites to enable persons with hearing impairments to utilize portable visual alarms and communication devices provided by the operator of the facility. |
||
807 Holding Cells and Housing Cells |
See Appendix 12.5 |
ANSI 806 Holding Cells and Housing Cells |
807.1 General. Holding cells and housing cells shall comply with 807. |
806.1 General. Holding cells and housing cells shall comply with Section 806. |
|
807.2 Cells with Mobility Features. Cells required to provide mobility features shall comply with 807.2. |
See Appendix 12.5.2 |
ANSI 806.2 Features for People Using Wheelchairs or Other Mobility Aids. Cells required to have features for people using wheelchairs or other mobility aids shall comply with Section 806.2. |
807.2.1 Turning Space. Turning space complying with 304 shall be provided within the cell. |
ANSI 806.2.1 Turning Space. Turning space complying with Section 304 shall be provided within the cell. |
|
807.2.2 Benches. Where benches are provided, at least one bench shall comply with 903. |
ANSI 806.2.2 Benches. Where benches are provided, at least one bench shall comply with Section 903. |
|
807.2.3 Beds. Where beds are provided, clear floor space complying with 305 shall be provided on at least one side of the bed. The clear floor space shall be positioned for parallel approach to the side of the bed. |
ANSI 806.2.3 Beds. Where beds are provided, clear floor space complying with Section 305 shall be provided on at least one side of the bed. The clear floor space shall be positioned for parallel approach to the side of the bed. |
|
807.2.4 Toilet and Bathing Facilities. Toilet facilities or bathing facilities that are provided as part of a cell shall comply with 603. Where provided, no fewer than one water closet, one lavatory, and one bathtub or shower shall comply with the applicable requirements of 603 through 610. |
ANSI 806.2.4 Toilet and Bathing Facilities. Toilet facilities or bathing facilities provided as part of a cell shall comply with Section 603. |
|
807.3 Cells with Communication Features. Cells required to provide communication features shall comply with 807.3. |
See Appendix 12.6 |
ANSI 806.3 Communication Features. Cells required to have communication features shall comply with Section 806.3. |
807.3.1 Alarms. Where audible emergency alarm systems are provided to serve the occupants of cells, visible alarms complying with 702 shall be provided. EXCEPTION: Visible alarms shall not be required where inmates or detainees are not allowed independent means of egress. |
ANSI 806.3.1 Alarms. Where audible emergency alarm systems are provided to serve the occupants of cells, visual alarms complying with Section 702 shall be provided. EXCEPTION: In cells where inmates or detainees are not allowed independent means of egress, visual alarms shall not be required. |
|
807.3.2 Telephones. Telephones, where provided within cells, shall have volume controls complying with 704.3. |
ANSI 806.3.2 Telephones. Where provided, telephones within cells shall have volume controls complying with Section 704.3. |
|
808 Courtrooms |
See Appendix 11.2.1 |
ANSI 807 Courtrooms |
808.1 General. Courtrooms shall comply with 808. |
ANSI 807.1 General. Courtrooms shall comply with Section 807. |
|
808.2 Turning Space. Where provided, areas that are raised or depressed and accessed by ramps or platform lifts with entry ramps shall provide unobstructed turning space complying with 304. |
ANSI 807.2 Turning Space. Where provided, each area that is raised or depressed and accessed by ramps or platform lifts with entry ramps shall provide an unobstructed turning space complying with Section 304. |
|
808.3 Clear Floor Space. Each jury box and witness stand shall have, within its defined area, clear floor space complying with 305. EXCEPTION: In alterations, wheelchair spaces are not required to be located within the defined area of raised jury boxes or witness stands and shall be permitted to be located outside these spaces where ramp or platform lift access poses a hazard by restricting or projecting into a means of egress required by the appropriate administrative authority. |
ANSI 807.3 Clear Floor Space. Within the defined area of each jury box and witness stand, a clear floor space complying with Section 305 shall be provided. EXCEPTION: In alterations, wheelchair spaces are not required to be located within the defined area of raised jury boxes or witness stands and shall be permitted to be located outside these spaces where ramps or platform lifts restrict or project into the means of egress required by the administrative authority. |
|
808.4 Judges' Benches and Courtroom Stations. Judges' benches, clerks' stations, bailiffs' stations, deputy clerks' stations, court reporters' stations and litigants' and counsel stations shall comply with 902. |
ANSI 807.4 Judges' Benches and Courtroom Stations. Judges' benches, clerks' stations, bailiffs' stations, deputy clerks' stations, court reporters' stations and litigants' and counsel stations shall comply with Section 902. |
|
809 Residential Dwelling Units |
ANSI Chapter 10. Dwelling Units and Sleeping Units |
|
ANSI 1001 General |
||
ANSI 1001.1 Scoping. Dwelling units and sleeping units required to be Accessible units, Type A units, Type B units, or units with accessible communication features by the scoping provisions adopted by the administrative authority shall comply with the applicable provisions of Chapter 10. |
||
ANSI 1003 Type A Units |
||
809.1 General. Residential dwelling units shall comply with 809. Residential dwelling units required to provide mobility features shall comply with 809.2 through 809.4. Residential dwelling units required to provide communication features shall comply with 809.5. |
ANSI 1003.1 General. Type A units shall comply with Section 1003. |
|
ANSI 1003.2 Primary Entrance. The accessible primary entrance shall be on an accessible route from public and common areas. The primary entrance shall not be to a bedroom. |
||
809.2 Accessible Routes. Accessible routes complying with Chapter 4 shall be provided within residential dwelling units in accordance with 809.2. EXCEPTION: Accessible routes shall not be required to or within unfinished attics or unfinished basements. |
ANSI 1003.3 Accessible Route. Accessible routes within Type A units shall comply with Section 1003.3. Exterior spaces less than 30 inches (760 mm) in depth or width shall comply with Sections 1003.3.1, 1003.3.3, 302, and 303. |
|
809.2.1 Location. At least one accessible route shall connect all spaces and elements which are a part of the residential dwelling unit. Where only one accessible route is provided, it shall not pass through bathrooms, closets, or similar spaces. |
ANSI 1003.3.1 Location. At least one accessible route shall connect all spaces and elements that are a part of the unit. Where only one accessible route is provided, it shall not pass through bathrooms and toilet rooms, closets, or similar spaces. EXCEPTION: An accessible route is not required to unfinished attics and unfinished basements that are part of the unit. |
|
809.2.2 Turning Space. All rooms served by an accessible route shall provide a turning space complying with 304. EXCEPTION: Turning space shall not be required in exterior spaces 30 inches (760 mm) maximum in depth or width. |
ANSI 1003.3.2 Turning Space. All rooms served by an accessible route shall provide a turning space complying with Section 304. EXCEPTION: Toilet rooms and bathrooms that are not required to comply with Section 1003.11. |
|
ANSI 1003.3.3 Components. Accessible routes shall consist of one or more of the following elements: walking surfaces with a slope not steeper than 1:20, ramps, elevators, and platform lifts. |
||
ANSI 1003.4 Walking Surfaces. Walking surfaces that are part of an accessible route shall comply with Section 403. |
||
ANSI 1003.5 Doors and Doorways. The primary entrance door to the unit, and all other doorways intended for user passage, shall comply with Section 404. EXCEPTIONS: 1. Thresholds at exterior sliding doors shall be permitted to be 3/4 inch (19 mm) maximum in height, provided they are beveled with a slope not greater than 1:2. 2. In toilet rooms and bathrooms not required to comply with Section 1003.11, maneuvering clearances required by Section 404.2.3 are not required on the toilet room or bathroom side of the door. |
||
ANSI 1003.6 Ramps. Ramps shall comply with Section 405. |
||
ANSI 1003.7 Elevators. Elevators within the unit shall comply with Section 407, 408, or 409. |
||
ANSI 1003.8 Platform Lifts. Platform lifts within the unit shall comply with Section 410. |
||
ANSI 1003.9 Operable Parts. Lighting controls, electrical switches and receptacle outlets, environmental controls, appliance controls, operating hardware for operable windows, plumbing fixture controls, and user controls for security or intercom systems shall comply with Section 309. EXCEPTIONS: 1. Receptacle outlets serving a dedicated use. 2. One receptacle outlet is not required to comply with Section 309 where all of the following conditions are met: (a) the receptacle outlet is above a length of countertop that is uninterrupted by a sink or appliance; and (b) at least one receptacle outlet complying with Section 1003.9 is provided for that length of countertop; and (c) all other receptacle outlets provided for that length of countertop comply with Section 1003.9. 3. Floor receptacle outlets. 4. HVAC diffusers. 5. Controls mounted on ceiling fans. 6. Where redundant controls other than light switches are provided for a single element, one control in each space shall not be required to be accessible. |
||
ANSI 1003.10 Laundry Equipment. Washing machines and clothes dryers shall comply with Section 611. |
||
809.3 Kitchen. Where a kitchen is provided, it shall comply with 804. Note: Some of the special features in kitchens, referred to as "adaptable" in earlier editions of that standard, are located as exceptions in section 804 of new ADAAG. |
ANSI 1003.12 Kitchens. Kitchens shall comply with Section 1003.12. |
|
ANSI 1003.12.1 Clearance. Clearance complying with Section 1003.12.1 shall be provided. |
||
ANSI 1003.12.1.1 Minimum Clearance. Clearance between all opposing base cabinets, counter tops, appliances, or walls within kitchen work areas shall be 40 inches (1015 mm) minimum. |
||
ANSI 1003.12.1.2 U–Shaped Kitchens. In kitchens with counters, appliances, or cabinets on three contiguous sides, clearance between all opposing base cabinets, countertops, appliances, or walls within kitchen work areas shall be 60 inches (1525 mm) minimum. |
||
ANSI 1003.12.2 Clear Floor Space. Clear floor spaces required by Sections 1003.12.3 through 1003.12.6 shall comply with Section 305. |
||
ANSI 1003.12.3 Work Surface. At least one section of counter shall provide a work surface 30 inches (760 mm) minimum in length complying with Section 1003.12.3. |
||
ANSI 1003.12.3.1 Clear Floor Space. A clear floor space, positioned for a forward approach to the work surface, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The clear floor space shall be centered on the work surface. EXCEPTION: Cabinetry shall be permitted under the work surface, provided: (a) the cabinetry can be removed without removal or replacement of the work surface, (b) the floor finish extends under such cabinetry, and (c) the walls behind and surrounding cabinetry are finished. |
||
ANSI 1003.12.3.2 Height. The work surface shall be 34 inches (865 mm) maximum above the floor. EXCEPTION: A counter that is adjustable to provide a work surface at variable heights 29 inches (735 mm) minimum and 36 inches (915 mm) maximum above the floor, or that can be relocated within that range without cutting the counter or damaging adjacent cabinets, walls, doors, and structural elements, shall be permitted. |
||
ANSI 1003.12.3.3 Exposed Surfaces. There shall be no sharp or abrasive surfaces under the exposed portions of work surface counters. |
||
ANSI 1003.12.4 Sink. Sinks shall comply with Section 1003.12.4. |
||
ANSI 1003.12.4.1 Clear Floor Space. A clear floor space, positioned for a forward approach to the sink, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The clear floor space shall be centered on the sink bowl. EXCEPTIONS: 1. The requirement for knee and toe clearance shall not apply to more than one bowl of a multi–bowl sink. 2. Cabinetry shall be permitted to be added under the sink, provided: (a) the cabinetry can be removed without removal or replacement of the sink, (b) the floor finish extends under such cabinetry, and (c) the walls behind and surrounding cabinetry are finished. |
||
ANSI 1003.12.4.2 Height. The front of the sink shall be 34 inches (865 mm) maximum above the floor, measured to the higher of the rim or counter surface. EXCEPTION: A sink and counter that is adjustable to variable heights 29 inches (735 mm) minimum and 36 inches (915 mm) maximum above the floor, or that can be relocated within that range without cutting the counter or damagingadjacent cabinets, walls, doors and structural elements, provided rough–in plumbing permits connections of supply and drain pipes for sinks mounted at the height of 29 inches (735 mm), shall be permitted. |
||
ANSI 1003.12.4.3 Faucets. Faucets shall comply with Section 309. |
||
ANSI 1003.12.4.4 Exposed Pipes and Surfaces. Water supply and drain pipes under sinks shall be insulated or otherwise configured to protect against contact. There shall be no sharp or abrasive surfaces under sinks. |
||
ANSI 1003.12.5 Kitchen Storage. A clear floor space, positioned for a parallel or forward approach to the kitchen cabinets, shall be provided. |
||
ANSI 1003.12.6 Appliances. Where provided, kitchen appliances shall comply with Section 1003.12.6. |
||
ANSI 1003.12.6.1 Operable Parts. All appliance controls shall comply with Section 1003.9. EXCEPTIONS: 1. Appliance doors and door latching devices shall not be required to comply with Section 309.4. 2. Bottom–hinged appliance doors, when in the open position, shall not be required to comply with Section 309.3. |
||
ANSI 1003.12.6.2 Clear Floor Space. A clear floor space, positioned for a parallel or forward approach, shall be provided at each kitchen appliance. Clear floor spaces shall be permitted to overlap. |
||
ANSI 1003.12.6.3 Dishwasher. A clear floor space, positioned adjacent to the dishwasher door, shall be provided. The dishwasher door in the open position shall not obstruct the clear floor space for the dishwasher or an adjacent sink. |
||
ANSI 1003.12.6.4 Range or Cooktop. A clear floor space, positioned for a parallel or forward approach to the space for a range or cooktop, shall be provided. Where the clear floor space is positioned for a forward approach, knee and toe clearance complying with Section 306 shall be provided. Where knee and toe space is provided, the underside of the range or cooktop shall be insulated or otherwise configured to protect from burns, abrasions, or electrical shock. The location of controls shall not require reaching across burners. |
||
ANSI 1003.12.6.5 Oven. Ovens shall comply with Section 1003.12.6.5. Ovens shall have controls on front panels, on either side of the door. |
||
ANSI 1003.12.6.5.1 Side–Hinged Door Ovens. Side–hinged door ovens shall have a countertop positioned adjacent to the latch side of the oven door. |
||
ANSI 1003.12.6.5.2 Bottom–Hinged Door Ovens. Bottom–hinged door ovens shall have a countertop positioned adjacent to one side of the door. |
||
ANSI 1003.12.6.6 Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer 54 inches (1370 mm) maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches (610 mm) maximum from the centerline of the dedicated space. |
||
ANSI 1003.12.6.7 Trash Compactor. A clear floor space, positioned for a parallel or forward approach to the trash compactor, shall be provided. |
||
ANSI 1003.13 Windows. Where operable windows are provided, at least one window in each sleeping, living, or dining space shall have operable parts complying with Section 1003.9. Each required operable window shall have operable parts complying with Section 1003.9. |
||
ANSI 1003.14 Storage Facilities. Where storage facilities are provided, they shall comply with Section 1003.14. Kitchen cabinets shall comply with Section 1003.12.5. |
||
ANSI 1003.14.1 Clear Floor Space. A clear floor space complying with Section 305, positioned for a parallel or forward approach, shall be provided at each storage facility. |
||
ANSI 1003.14.2 Height. A portion of the storage area of each storage facility shall comply with at least one of the reach ranges specified in Section 308. |
||
ANSI 1003.14.3 Operable Parts. Operable parts on storage facilities shall comply with Section 309. |
||
809.4 Toilet Facilities and Bathing Facilities. At least one bathroom shall comply with 603. No fewer than one of each type of fixture provided shall comply with applicable requirements of 603 through 610. Toilet and bathing fixtures required to comply with 603 through 610 shall be located in the same toilet and bathing area, such that travel between fixtures does not require travel between other parts of the residential dwelling unit. Note: Many of the special features in ANSI toilet and bathing facilities, referred to as "adaptable" in earlier editions of that standard, are located as exceptions in sections 603 through 610 of new ADAAG. |
ANSI 1003.11 Toilet and Bathing Facilities. |
|
ANSI 1003.11.1 General. All toilet and bathing areas shall comply with Section 1003.11.4. At least one toilet and bathing facility shall comply with Section 1003.11. At least one lavatory, one water closet and either a bathtub or shower within the unit shall comply with Section 1003.11. The accessible toilet and bathing fixtures shall be in a single toilet/bathing area, such that travel between fixtures does not require travel through other parts of the unit. |
||
ANSI 1003.11.2 Doors. Doors shall not swing into the clear floor space or clearance for any fixture. EXCEPTION: Where a clear floor space complying with Section 305.3 is provided within the room beyond the arc of the door swing. |
||
ANSI 1003.11.3 Overlap. Clear floor spaces, clearances at fixtures and turning spaces are permitted to overlap. |
||
ANSI 1003.11.4 Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Sections 604.5, 607.4, 608.3 and 608.4, reinforcement shall be provided for the future installation of grab bars and seats meeting those requirements. EXCEPTION: Reinforcement is not required in a room containing only a lavatory and a water closet, provided the room does not contain the only lavatory or water closet on the accessible level of the dwelling unit. |
||
ANSI 1003.11.5 Lavatory. Lavatories shall comply with Section 606. EXCEPTION: Cabinetry shall be permitted under the lavatory, provided: (a) the cabinetry can be removed without removal or replacement of the lavatory; (b) the floor finish extends under such cabinetry; and (c) the walls behind and surrounding cabinetry are finished. |
||
ANSI 1003.11.6 Mirrors. Mirrors above lavatories shall have the bottom edge of the reflecting surface 40 inches (1015 mm) maximum above the floor. |
||
ANSI 1003.11.7 Water Closet. Water closets shall comply with Section 1003.11.7. |
||
ANSI 1003.11.7.1 Location. The water closet shall be positioned with a wall to the rear and to one side. The centerline of the water closet shall be 16 inches (405 mm) minimum and 18 inches (455 mm) maximum from the sidewall. |
||
ANSI 1003.11.7.2 Clearance. A clearance around the water closet of 60 inches (1525 mm) minimum, measured perpendicular from the side wall, and 56 inches (1420 mm) minimum, measured perpendicular from the rear wall, shall be provided. |
||
ANSI 1003.11.7.3 Overlap. The required clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, paper dispensers, coat hooks, shelves, accessible routes, clear floor space required at other fixtures, and the wheelchair turning space. No other fixtures or obstructions shall be located within the required water closet clearance. EXCEPTION: A lavatory complying with Section 1003.11.5 shall be permitted on the rear wall 18 inches (455 mm) minimum from the centerline of the water closet where the clearance at the water closet is 66 inches (1675 mm) minimum measured perpendicular from the rear wall. |
||
ANSI 1003.11.7.4 Height. The top of the water closet seat shall be 15 inches (380 mm) minimum and 19 inches (485 mm) maximum above the floor, measured to the top of the seat. |
||
ANSI 1003.11.7.5 Flush Controls. Hand operated flush controls shall comply with Section 1003.9. Flush controls shall be located on the open side of the water closet. |
||
ANSI 1003.11.8 Bathtub. Bathtubs shall comply with Section 607. EXCEPTIONS: 1. The removable in–tub seat required by Section 607.3 is not required. 2. Counter tops and cabinetry shall be permitted at the control end of the clearance, provided such counter tops and cabinetry can be removed and the floor finish extends under such cabinetry. |
||
ANSI 1003.11.9 Shower. Showers shall comply with Section 608. EXCEPTION: Counter tops and cabinetry shall be permitted at the control end of the clearance, provided such counter tops and cabinetry can be removed and the floor finish extends under such cabinetry. |
||
809.5 Residential Dwelling Units with Communication Features. Residential dwelling units required to provide communication features shall comply with 809.5. |
ANSI 1005 Units with Accessible Communication Features |
|
ANSI 1005.1 General. Units required to have accessible communication features shall comply with Section 1005. |
||
809.5.1 Building Fire Alarm System. Where a building fire alarm system is provided, the system wiring shall be extended to a point within the residential dwelling unit in the vicinity of the residential dwelling unit smoke detection system. |
ANSI 1005.3 Building Fire Alarm System. Where a building fire alarm system is provided, the system wiring shall be extended to a point within the unit in the vicinity of the unit smoke detection system. |
|
809.5.1.1 Alarm Appliances. Where alarm appliances are provided within a residential dwelling unit as part of the building fire alarm system, they shall comply with 702. |
ANSI 1005.4 Visible Notification Appliances. Visible notification appliances, where provided within the unit as part of the unit smoke detection system or the building fire alarm system, shall comply with Section 1005.4. |
|
ANSI 1005.4.1 Appliance. Visible notification appliances shall comply with Section 702. |
||
809.5.1.2 Activation. All visible alarm appliances provided within the residential dwelling unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion of the building containing the residential dwelling unit. |
ANSI 1005.4.2 Activation. All visible notification appliances provided within the unit for smoke detection notification shall be activated upon smoke detection. All visible notification appliances provided within the unit for building fire alarm notification shall be activated upon activation of the building fire alarm in the portion of the building containing the unit. |
|
809.5.2 Residential Dwelling Unit Smoke Detection System. Residential dwelling unit smoke detection systems shall comply with NFPA 72 (1999 or 2002 edition) (incorporated by reference, see "Referenced Standards" in Chapter 1). |
ANSI 1005.2 Unit Smoke Detection. Where provided, unit smoke detection shall include audible notification complying with NFPA 72 listed in Section 105.2.2. |
|
809.5.2.2 Activation. All visible alarm appliances provided within the residential dwelling unit for smoke detection notification shall be activated upon smoke detection. |
||
809.5.3 Interconnection. The same visible alarm appliances shall be permitted to provide notification of residential dwelling unit smoke detection and building fire alarm activation. |
ANSI 1005.4.3 Interconnection. The same visible notification appliances shall be permitted to provide notification of unit smoke detection and building fire alarm activation. |
|
809.5.4 Prohibited Use. Visible alarm appliances used to indicate residential dwelling unit smoke detection or building fire alarm activation shall not be used for any other purpose within the residential dwelling unit. |
ANSI 1005.4.4 Prohibited Use. Visible notification appliances used to indicate unit smoke detection or building fire alarm activation shall not be used for any other purpose within the unit. |
|
809.5.5 Residential Dwelling Unit Primary Entrance. Communication features shall be provided at the residential dwelling unit primary entrance complying with 809.5.5. |
ANSI 1005.5 Unit Primary Entrance. Communication features shall be provided at the unit primary entrance complying with Section 1005.5. |
|
809.5.5.1 Notification. A hard-wired electric doorbell shall be provided. A button or switch shall be provided outside the residential dwelling unit primary entrance. Activation of the button or switch shall initiate an audible tone and visible signal within the residential dwelling unit. Where visible doorbell signals are located in sleeping areas, they shall have controls to deactivate the signal. |
ANSI 1005.5.1 Notification. A hard–wired electric doorbell shall be provided. A button or switch shall be provided on the public side of the unit primary entrance. Activation of the button or switch shall initiate an audible tone within the unit. |
|
809.5.5.2 Identification. A means for visually identifying a visitor without opening the residential dwelling unit entry door shall be provided and shall allow for a minimum 180 degree range of view. |
ANSI 1005.5.2 Identification. A means for visually identifying a visitor without opening the unit entry door shall be provided. Peepholes, where used, shall provide a minimum 180–degree range of view. |
|
809.5.6 Site, Building, or Floor Entrance. Where a system, including a closed-circuit system, permitting voice communication between a visitor and the occupant of the residential dwelling unit is provided, the system shall comply with 708.4. |
ANSI 1005.6 Site, Building, or Floor Entrance. Where a system permitting voice communication between a visitor and the occupant of the unit is provided at a location other than the unit entry door, the system shall comply with Section 1005.6. |
|
ANSI 1005.6.1 Public or Common–Use Interface. The public or common–use system interface shall include the capability of supporting voice and TTY communication with the unit interface. |
||
ANSI 1005.6.2 Unit Interface. The unit system interface shall include a telephone jack capable of supporting voice and TTY communication with the public or common–use system interface. |
||
ANSI 1005.7 Closed–Circuit Communication Systems. Where a closed–circuit communication system is provided, the public or common–use system interface shall comply with Section 1005.6.1, and the unit system interface in units required to have accessible communication features shall comply with Section 1005.6.2. |
||
ANSI 1004 Type B Units |
||
ANSI 1004.1 General. Type B units shall comply with Section 1004. |
||
ANSI 1004.2 Primary Entrance. The accessible primary entrance shall be on an accessible route from public and common areas. The primary entrance shall not be to a bedroom. |
||
ANSI 1004.3 Accessible Route. Accessible routes within Type B units shall comply with Section 1004.3. |
||
ANSI 1004.3.1 Location. At least one accessible route shall connect all spaces and elements that are a part of the unit. Where only one accessible route is provided, it shall not pass through bathrooms and toilet rooms, closets, or similar spaces. EXCEPTION: One of the following is not required to be on an accessible route: 1. A raised floor area in a portion of a living, dining, or sleeping room; or 2. A sunken floor area in a portion of a living, dining, or sleeping room; or 3. A mezzanine that does not have plumbing fixtures or an enclosed habitable space. |
||
ANSI 1004.3.2 Components. Accessible routes shall consist of one or more of the following elements: walking surfaces with a slope not steeper than 1:20, doorways, ramps, elevators, and platform lifts. |
||
ANSI 1004.4 Walking Surfaces. Walking surfaces that are part of an accessible route shall comply with Section 1004.4. |
||
ANSI 1004.4.1 Width. Clear width of an accessible route shall comply with Section 403.5. |
||
ANSI 1004.4.2 Changes in Level. Changes in level shall comply with Section 303. EXCEPTION: Where exterior deck, patio or balcony surface materials are impervious, the finished exterior impervious surface shall be 4 inches (100 mm) maximum below the floor level of the adjacent interior spaces of the unit. |
||
ANSI 1004.5 Doors and Doorways. Doors and doorways shall comply with Section 1004.5. |
||
ANSI 1004.5.1 Primary Entrance Door. The primary entrance door to the unit shall comply with Section 404. EXCEPTION: Maneuvering clearances required by Section 404.2.3 shall not be required on the unit side of the primary entrance door. |
||
ANSI 1004.5.2 User Passage Doorways. Doorways intended for user passage shall comply with Section 1004.5.2. |
||
ANSI 1004.5.2.1 Clear Width. Doorways shall have a clear opening of 313/4 inches (810 mm) minimum. Clear opening of swinging doors shall be measured between the face of the door and stop, with the door open 90 degrees. |
||
ANSI 1004.5.2.2 Thresholds. Thresholds shall comply with Section 303. EXCEPTION: Thresholds at exterior sliding doors shall be permitted to be 3/4 inch (19 mm) maximum in height, provided they are beveled with a slope not steeper than 1:2. |
||
ANSI 1004.5.2.3 Automatic Doors. Automatic doors shall comply with Section 404.3. |
||
ANSI 1004.5.2.4 Double Leaf Doorways. Where an inactive leaf with operable parts higher than 48 inches (1220 mm) or lower than 15 inches (380 mm) above the floor is provided, the active leaf shall provide the clearance required by Section 1004.5.2.1. |
||
ANSI 1004.6 Ramps. Ramps shall comply with Section 405. |
||
ANSI 1004.7 Elevators. Elevators within the unit shall comply with Section 407, 408, or 409. |
||
ANSI 1004.8 Platform Lifts. Platform lifts within the unit shall comply with Section 410. |
||
ANSI 1004.9 Operable Parts. Lighting controls, electrical switches and receptacle outlets, environmental controls, and user controls for security or intercom systems shall comply with Sections 309.2 and 309.3. EXCEPTIONS: 1. Receptacle outlets serving a dedicated use. 2. One receptacle outlet is not required to comply with Sections 309.2 and 309.3 where all of the following conditions are met: (a) the receptacle outlet is above a length of countertop that is uninterrupted by a sink or appliance; and (b) at least one receptacle outlet complying with Section 1004.9 is provided for that length of countertop; and (c) all other receptacle outlets provided for that length of countertop comply with Section 1004.9. 3. Floor receptacle outlets. 4. HVAC diffusers. 5. Controls mounted on ceiling fans. 6. Controls or switches mounted on appliances. 7. Plumbing fixture controls. |
||
ANSI 1004.10 Laundry Equipment. Washing machines and clothes dryers shall comply with Section 1004.10. |
||
ANSI 1004.10.1 Clear Floor Space. A clear floor space complying with Section 305.3, positioned for parallel approach, shall be provided. The clear floor space shall be centered on the appliance. |
||
ANSI 1004.11 Toilet and Bathing Facilities. Toilet and bathing fixtures shall comply with Section 1004.11. EXCEPTION: Fixtures on levels not required to be accessible. |
||
ANSI 1004.11.1 Clear Floor Space. Clear floor space required by Section 1004.11.3.1 or 1004.11.3.2 shall comply with Sections 1004.11.1 and 305.3. |
||
ANSI 1004.11.1.1 Doors. Doors shall not swing into the clear floor space for any fixture. EXCEPTION: Where a clear floor space complying with Section 305.3, excluding knee and toe clearances under elements, is provided within the room beyond the arc of the door swing. |
||
ANSI 1004.11.1.2 Knee and Toe Clearance. Clear floor space at fixtures shall be permitted to include knee and toe clearances complying with Section 306. |
||
ANSI 1004.11.1.3 Overlap. Clear floor spaces shall be permitted to overlap. |
||
ANSI 1004.11.2 Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Sections 604.5, 607.4, 608.3 and 608.4, reinforcement shall be provided for the future installation of grab bars and seats meeting those requirements. EXCEPTION: Reinforcement is not required in a room containing only a lavatory and a water closet, provided the room does not contain the only lavatory or water closet on the accessible level of the unit. |
||
ANSI 1004.11.3 Toilet and Bathing Rooms. Either all toilet and bathing rooms provided shall comply with Section 1004.11.3.1 (Option A), or one toilet and bathing room shall comply with Section 1004.11.3.2 (Option B). |
||
ANSI 1004.11.3.1 Option A. Each fixture provided shall comply with Section 1004.11.3.1. EXCEPTION: A lavatory and a water closet in a room containing only a lavatory and water closet, provided the room does not contain the only lavatory or water closet on the accessible level of the unit. |
||
ANSI 1004.11.3.1.1 Lavatory. A clear floor space complying with Section 305.3, positioned for a parallel approach, shall be provided. The clear floor space shall be centered on the lavatory. EXCEPTIONS: 1. A lavatory complying with Section 606. 2. Cabinetry shall be permitted under the lavatory provided such cabinetry can be removed without removal or replacement of the lavatory, and the floor finish extends under such cabinetry. |
||
ANSI 1004.11.3.1.2 Water Closet. The lateral distance from the centerline of the water closet to a bathtub or lavatory shall be 18 inches (455 mm) minimum on the side opposite the direction of approach and 15 inches (380 mm) minimum on the other side. The lateral distance from the centerline of the water closet to an adjacent wall shall be 18 inches (455 mm). The lateral distance from the centerline of the water closet to a lavatory or bathtub shall be 15 inches (380 mm) minimum. The water closet shall be positioned to allow for future installation of a grab bar on the side with 18 inches (455 mm) clearance. Clearance around the water closet shall comply with Section 1004.11.3.1.2.1, 1004.11.3.1.2.2, or 1004.11.3.1.2.3. |
||
ANSI 1004.11.3.1.2.1 Parallel Approach. A clearance 56 inches (1420 mm) minimum measured from the wall behind the water closet, and 48 inches (1220 mm) minimum measured from a point 18 inches (455 mm) from the centerline of the water closet on the side designated for future installation of grab bars shall be provided. Vanities or lavatories on the wall behind the water closet are permitted to overlap the clearance. |
||
ANSI 1004.11.3.1.2.2 Forward Approach. A clearance 66 inches (1675 mm) minimum measured from the wall behind the water closet, and 48 inches (1220 mm) minimum measured from a point 18 inches (455 mm) from the centerline of the water closet on the side designated for future installation of grab bars shall be provided. Vanities or lavatories on the wall behind the water closet are permitted to overlap the clearance. |
||
ANSI 1004.11.3.1.2.3 Parallel or Forward Approach. A clearance 56 inches (1420 mm) minimum measured from the wall behind the water closet, and 42 inches (1065 mm) minimum measured from the centerline of the water closet shall be provided. |
||
ANSI 1004.11.3.1.3 Bathing Facilities. Where a bathtub or shower compartment is provided it shall conform with Section 1004.11.3.1.3.1, 1004.11.3.1.3.2, or 1004.11.3.1.3.3. |
||
ANSI 1004.11.3.1.3.1 Parallel Approach Bathtubs. A clearance 60 inches (1525 mm) minimum in length and 30 inches (760 mm) minimum in width shall be provided in front of bathtubs with a parallel approach. Lavatories complying with Section 606 shall be permitted in the clearance. A lavatory complying with Section 1004.11.3.1.1 shall be permitted at the control end of the bathtub if a clearance 48 inches (1220 mm) minimum in length and 30 inches (760 mm) minimum in width for a parallel approach is provided in front of the bathtub. |
||
ANSI 1004.11.3.1.3.2 Forward Approach Bathtubs. A clearance 60 inches (1525 mm) minimum in length and 48 inches (1220 mm) minimum in width shall be provided in front of bathtubs with a forward approach. A water closet shall be permitted in the clearance at the control end of the bathtub. |
||
ANSI 1004.11.3.1.3.3 Shower Compartment. If a shower compartment is the only bathing facility, the shower compartment shall have dimensions of 36 inches (915 mm) minimum in width and 36 inches (915 mm) minimum in depth. A clearance of 48 inches (1220 mm) minimum in length, measured perpendicular from the shower head wall, and 30 inches (760 mm) minimum in depth, measured from the face of the shower compartment, shall be provided. Reinforcing for a shower seat is not required in shower compartments larger than 36 inches (915 mm) in width and 36 inches (915 mm) in depth. |
||
ANSI 1004.11.3.2 Option B. One of each type of fixture provided shall comply with Section 1004.11.3.2. The accessible fixtures shall be in a single toilet/bathing area, such that travel between fixtures does not require travel through other parts of the unit. |
||
ANSI 1004.11.3.2.1 Lavatory. Lavatories shall comply with Section 1004.11.3.2.1. |
||
ANSI 1004.11.3.2.1.1 Clear Floor Space. A clear floor space complying with Section 305.3, positioned for a parallel approach, shall be provided. EXCEPTIONS: 1. A lavatory complying with Section 606. 2. Cabinetry shall be permitted under the lavatory, provided such cabinetry can be removed without removal or replacement of the lavatory, and the floor finish extends under such cabinetry. |
||
ANSI 1004.11.3.2.1.2 Position. The clear floor space shall be centered on the lavatory. |
||
ANSI 1004.11.3.2.1.3 Height. The front of the lavatory shall be 34 inches (865 mm) maximum above the floor, measured to the higher of the fixture rim or counter surface. |
||
ANSI 1004.11.3.2.2 Water Closet. The water closet shall comply with Section 1004.11.3.1.2. |
||
ANSI 1004.11.3.2.3 Bathing Facilities. Where either a bathtub or shower compartment is provided, it shall conform with Section 1004.11.3.2.3.1 or 1004.11.3.2.3.2. |
||
ANSI 1004.11.3.2.3.1 Bathtub. A clearance 48 inches (1220 mm) minimum in length measured perpendicular from the control end of the bathtub, and 30 inches (760 mm) minimum in width shall be provided in front of bathtubs. |
||
ANSI 1004.11.3.2.3.2 Shower Compartment. A shower compartment shall comply with Section 1004.11.3.1.3.3. |
||
ANSI 1004.12 Kitchens. Kitchens shall comply with Section 1004.12. |
||
ANSI 1004.12.1 Clearance. Clearance complying with Section 1004.12.1 shall be provided. |
||
ANSI 1004.12.1.1 Minimum Clearance. Clearance between all opposing base cabinets, counter tops, appliances, or walls within kitchen work areas shall be 40 inches (1015 mm) minimum. |
||
ANSI 1004.12.1.2 U–Shaped Kitchens. In kitchens with counters, appliances, or cabinets on three contiguous sides, clearance between all opposing base cabinets, countertops, appliances, or walls within kitchen work areas shall be 60 inches (1525 mm) minimum. |
||
ANSI 1004.12.2 Clear Floor Space. Clear floor space at appliances shall comply with Sections 1004.12.2 and 305.3. |
||
ANSI 1004.12.2.1 Sink. A clear floor space, positioned for a parallel approach to the sink, shall be provided. The clear floor space shall be centered on the sink bowl. EXCEPTION: Sinks complying with Section 606 shall be permitted to have a clear floor space positioned for a parallel or forward approach. |
||
ANSI 1004.12.2.2 Dishwasher. A clear floor space, positioned for a parallel or forward approach to the dishwasher, shall be provided. The clear floor space shall be positioned beyond the swing of the dishwasher door. |
||
ANSI 1004.12.2.3 Cooktop. A clear floor space, positioned for a parallel or forward approach to the cooktop, shall be provided. The centerline of the clear floor space shall align with the centerline of the cooktop. Where the clear floor space is positioned for a forward approach, knee and toe clearance complying with Section 306 shall be provided. Where knee and toe space is provided, the underside of the range or cooktop shall be insulated or otherwise configured to prevent burns, abrasions, or electrical shock. |
||
ANSI 1004.12.2.4 Oven. A clear floor space, positioned for a parallel or forward approach to the oven, shall be provided. |
||
ANSI 1004.12.2.5 Refrigerator/Freezer. A clear floor space, positioned for a parallel or forward approach to the refrigerator/freezer, shall be provided. |
||
ANSI 1004.12.2.6 Trash Compactor. A clear floor space, positioned for a parallel or forward approach to the trash compactor, shall be provided. |
||
810 Transportation Facilities |
ANSI 805 Transportation Facilities |
|
810.1 General. Transportation facilities shall comply with 810. |
10.1 General. Every station, bus stop, bus stop pad, terminal, building or other transportation facility, shall comply with the applicable provisions of 4.1 through 4.35, sections 5 through 9, and the applicable provisions of this section. The exception for elevators in 4.1.3(5), exception 1 and 4.1.6(1)(k) do not apply to a terminal, depot, or other station used for specific transportation, or an airport passenger terminal, or facilities subject to Title II. |
ANSI 805.1 General. Transportation facilities shall comply with Section 805. |
10.2 Bus Stops and Terminals |
||
10.2.1 New Construction |
||
810.2 Bus Boarding and Alighting Areas. Bus boarding and alighting areas shall comply with 810.2. |
10.2.1(1) Where new bus stop pads are constructed at bus stops, bays or other areas where a lift or ramp is to be deployed, they shall have a firm, stable surface; a minimum clear length of 96 inches (measured from the curb or vehicle roadway edge) and a minimum clear width of 60 inches (measured parallel to the vehicle roadway) to the maximum extent allowed by legal or site constraints; and shall be connected to streets, sidewalks or pedestrian paths by an accessible route complying with 4.3 and 4.4. The slope of the pad parallel to the roadway shall, to the extent practicable, be the same as the roadway. For water drainage, a maximum slope of 1:50 (2%) perpendicular to the roadway is allowed. |
IBC E108.2 Bus boarding and alighting areas. Bus boarding and alighting areas shall comply with Sections E108.2.1 through E108.2.4. |
ANSI 805.2 Bus Boarding and Alighting Areas. Bus boarding and alighting areas shall comply with Section 805.2. |
||
810.2.1 Surface. Bus stop boarding and alighting areas shall have a firm, stable surface. |
IBC E108.2.1 Surface. Bus boarding and alighting areas shall have a firm, stable surface. |
|
ANSI 805.2.1 Surface. Bus stop boarding and alighting areas shall have a firm, stable surface. |
||
810.2.2 Dimensions. Bus stop boarding and alighting areas shall provide a clear length of 96 inches (2440 mm) minimum, measured perpendicular to the curb or vehicle roadway edge, and a clear width of 60 inches (1525 mm) minimum, measured parallel to the vehicle roadway. |
IBC E108.2.2 Dimensions. Bus boarding and alighting areas shall have a clear length of 96 inches (2440 mm) minimum, measured perpendicular to the curb or vehicle roadway edge, and a clear width of 60 inches (1525 mm) minimum, measured parallel to the vehicle roadway. |
|
ANSI 805.2.2 Dimensions. Bus stop boarding and alighting areas shall have a 96 inches (2440 mm) minimum clear length, measured perpendicular to the curb or vehicle roadway edge, and a 60 inches (1525 mm) minimum clear width, measured parallel to the vehicle roadway. |
||
810.2.3 Connection. Bus stop boarding and alighting areas shall be connected to streets, sidewalks, or pedestrian paths by an accessible route complying with 402. |
IBC E108.2.3 Connection. Bus boarding and alighting areas shall be connected to streets, sidewalks or pedestrian paths by an accessible route complying with Section 1104. |
|
ANSI 805.2.4 Connection. Bus stop boarding and alighting areas shall be connected to streets, sidewalks, or pedestrian paths by an accessible route complying with Section 402. |
||
810.2.4 Slope. Parallel to the roadway, the slope of the bus stop boarding and alighting area shall be the same as the roadway, to the maximum extent practicable. Perpendicular to the roadway, the slope of the bus stop boarding and alighting area shall not be steeper than 1:48. |
IBC E108.2.4 Slope. Parallel to the roadway, the slope of the bus boarding and alighting area shall be the same as the roadway, to the maximum extent practicable. For water drainage, a maximum slope of 1:48 perpendicular to the roadway is allowed. |
|
ANSI 805.2.3 Slope. The slope of the bus stop boarding and alighting area parallel to the vehicle roadway shall be the same as the roadway, to the maximum extent practicable. The slope of the bus stop boarding and alighting area perpendicular to the vehicle roadway shall be 1:48 maximum. |
||
810.3 Bus Shelters. Bus shelters shall provide a minimum clear floor or ground space complying with 305 entirely within the shelter. Bus shelters shall be connected by an accessible route complying with 402 to a boarding and alighting area complying with 810.2. |
10.2.1(2) Where provided, new or replaced bus shelters shall be installed or positioned so as to permit a wheelchair or mobility aid user to enter from the public way and to reach a location, having a minimum clear floor area of 30 inches by 48 inches, entirely within the perimeter of the shelter. Such shelters shall be connected by an accessible route to the boarding area provided under paragraph (1) of this section. |
IBC E108.3 Bus shelters. Where provided, new or replaced bus shelters shall provide a minimum clear floor or ground space complying with ICC A117.1, Section 305, entirely within the shelter. Such shelters shall be connected by an accessible route to the boarding area required by Section E108.2. |
ANSI 805.3 Bus Shelters. Bus shelters shall provide a minimum clear floor space complying with Section 305 entirely within the shelter. Bus shelters shall be connected by an accessible route complying with Section 402 to a boarding and alighting area complying with Section 805.2. |
||
810.4 Bus Signs. Bus route identification signs shall comply with 703.5.1 through 703.5.4, and 703.5.7 and 703.5.8. In addition, to the maximum extent practicable, bus route identification signs shall comply with 703.5.5. EXCEPTION: Bus schedules, timetables and maps that are posted at the bus stop or bus bay shall not be required to comply. |
10.2.1(3) Where provided, all new bus route identification signs shall comply with 4.30.5. In addition, to the maximum extent practicable, all new bus route identification signs shall comply with 4.30.2 and 4.30.3. Signs that are sized to the maximum dimensions permitted under legitimate local, state or federal regulations or ordinances shall be considered in compliance with 4.30.2 and 4.30.3 for purposes of this section. EXCEPTION: Bus schedules, timetables, or maps that are posted at the bus stop or bus bay are not required to comply with this provision. |
IBC E108.4 Signs. New bus route identification signs shall have finish and contrast complying with ICC A117.1. Additionally, to the maximum extent practicable, new bus route identification signs shall provide visual characters complying with ICC A117.1. EXECPTION: Bus schedules, timetables and maps that are posted at the bus stop or bus bay are not required to meet this requirement. |
ANSI 805.4 Bus Signs. Bus route identification signs shall have visual characters complying with Sections 703.2.2, 703.2.3, and 703.2.5 through 703.2.8. In addition, bus route identification numbers shall be visual characters complying with Section 703.2.4. EXCEPTION: Bus schedules, timetables and maps that are posted at the bus stop or bus bay shall not be required to comply with Section 805.4. |
||
10.2.2 Bus Stop Siting and Alterations. (1) Bus stop sites shall be chosen such that, to the maximum extent practicable, the areas where lifts or ramps are to be deployed comply with section 10.2.1(1) and (2). (2) When new bus route identification signs are installed or old signs are replaced, they shall comply with the requirements of 10.2.1(3). |
E108.5 Bus stop siting. Bus stop sites shall be chosen such that, to the maximum extent practicable, the area where ramps or lifts are to be deployed comply with Sections E108.2 and E108.3. |
|
810.5 Rail Platforms. Rail platforms shall comply with 810.5. |
ANSI 805.5 Rail Platforms. Rail platforms shall comply with Section 805.5. |
|
810.5.1 Slope. Rail platforms shall not exceed a slope of 1:48 in all directions. EXCEPTION: Where platforms serve vehicles operating on existing track or track laid in existing roadway, the slope of the platform parallel to the track shall be permitted to be equal to the slope (grade) of the roadway or existing track. |
ANSI 805.5.1 Slope. Rail platforms shall not exceed a slope of 1:48 in all directions. EXCEPTION: Where platforms serve vehicles operating on existing track or track laid in existing roadway, the slope of the platform parallel to the track shall be permitted to be equal to the slope (grade) of the roadway or existing track. |
|
810.5.2 Detectable Warnings. Platform boarding edges not protected by platform screens or guards shall have detectable warnings complying with 705 along the full length of the public use area of the platform. |
10.3.1(8) Platform edges bordering a drop-off and not protected by platform screens or guard rails shall have a detectable warning. Such detectable warnings shall comply with 4.29.2 and shall be 24 inches wide running the full length of the platform drop-off. |
IBC 1109.9 Detectable warnings. Passenger transit platform edges bordering a drop-off and not protected by platform screens or guards shall have a detectable warning. Exception: Detectable warnings are not required at bus stops. |
ANSI 805.5.2 Detectable Warnings. Platform boarding edges not protected by platform screens or guards shall have a detectable warning complying with Section 705, 24 inches (610 mm) in width, along the full length of the public use area of the platform. |
||
810.5.3 Platform and Vehicle Floor Coordination. Station platforms shall be positioned to coordinate with vehicles in accordance with the applicable requirements of 36 CFR Part 1192. Low-level platforms shall be 8 inches (205 mm) minimum above top of rail. EXCEPTION: Where vehicles are boarded from sidewalks or street-level, low-level platforms shall be permitted to be less than 8 inches (205 mm). |
10.3.1(9) In stations covered by this section, rail-to-platform height in new stations shall be coordinated with the floor height of new vehicles so that the vertical difference, measured when the vehicle is at rest, is within plus or minus 5/8 inch under normal passenger load conditions. For rapid rail, light rail, commuter rail, high speed rail, and intercity rail systems in new stations, the horizontal gap, measured when the new vehicle is at rest, shall be no greater than 3 inches. For slow moving automated guideway "people mover" transit systems, the horizontal gap in new stations shall be no greater than 1 inch. EXCEPTION 1: Existing vehicles operating in new stations may have a vertical difference with respect to the new platform within plus or minus 1-1/2 inches. EXCEPTION 2: In light rail, commuter rail and intercity rail systems where it is not operationally or structurally feasible to meet the horizontal gap or vertical difference requirements, mini-high platforms, car-borne or platform-mounted lifts, ramps or bridge plates, or similar manually deployed devices, meeting the applicable requirements of 36 C.F.R. part 1192, or 49 C.F.R. part 38 shall suffice. |
IBC E109.2.4 Rail-to-platform height. Station platforms shall be positioned to coordinate with vehicles in accordance with the applicable provisions of 36 CFR, Part 1192. Low-level platforms shall be 8 inches (250 mm) minimum above top of rail. Exception: Where vehicles are boarded from sidewalks or street level, low-level platforms shall be permitted to be less than 8 inches (250 mm). |
810.6 Rail Station Signs. Rail station signs shall comply with 810.6. EXCEPTION. Signs shall not be required to comply with 810.6.1 and 810.6.2 where audible signs are remotely transmitted to hand-held receivers, or are user- or proximity-actuated. |
IBC E109.2.2 Signs. Signage in fixed transportation facilities and stations shall comply with Sections E109.2.2.1 through E109.2.2.3. |
|
ANSI 805.6 Rail Station Signs. Rail station signs shall comply with Section 805.6. EXCEPTION: Signs shall not be required to comply with Sections 805.6.1 and 805.6.2 where audible signs are remotely transmitted to hand–held receivers, or are user– or proximity–actuated. |
||
810.6.1 Entrances. Where signs identify a station or its entrance, at least one sign at each entrance shall comply with 703.2 and shall be placed in uniform locations to the maximum extent practicable. Where signs identify a station that has no defined entrance, at least one sign shall comply with 703.2 and shall be placed in a central location. |
10.3.1(4) Where signs are provided at entrances to stations identifying the station or the entrance, or both, at least one sign at each entrance shall comply with 4.30.4 and 4.30.6. Such signs shall be placed in uniform locations at entrances within the transit system to the maximum extent practicable. EXCEPTION: Where the station has no defined entrance, but signage is provided, then the accessible signage shall be placed in a central location. |
IBC E109.2.2.1 Tactile signs. Where signs are provided at entrances to stations identifying the station or the entrance, or both, at least one sign at each entrance shall be tactile. A minimum of one tactile sign identifying the specific station shall be provided on each platform or boarding area. Such signs shall be placed in uniform locations at entrances and on platforms or boarding areas within the transit system to the maximum extent practicable. Tactile signs shall comply with ICC A117.1. Exceptions: 1. Where the station has no defined entrance but signs are provided, the tactile signs shall be placed in a central location. 2. Signs are not required to be tactile where audible signs are remotely transmitted to hand-held receivers, or are user or proximity actuated. |
ANSI 805.6.1 Entrances. Where signs identify a station or a station entrance, at least one sign with tactile characters complying with Section 703.3 shall be provided at each entrance. |
||
810.6.2 Routes and Destinations. Lists of stations, routes and destinations served by the station which are located on boarding areas, platforms, or mezzanines shall comply with 703.5. At least one tactile sign identifying the specific station and complying with 703.2 shall be provided on each platform or boarding area. Signs covered by this requirement shall, to the maximum extent practicable, be placed in uniform locations within the system. EXCEPTION: Where sign space is limited, characters shall not be required to exceed 3 inches (75 mm). |
10.3.1(6) Lists of stations, routes, or destinations served by the station and located on boarding areas, platforms, or mezzanines shall comply with 4.30.1, 4.30.2, 4.30.3, and 4.30.5. A minimum of one sign identifying the specific station and complying with 4.30.4 and 4.30.6 shall be provided on each platform or boarding area. All signs referenced in this paragraph shall, to the maximum extent practicable, be placed in uniform locations within the transit system. |
IBC E109.2.2.3 Informational signs. Lists of stations, routes and destinations served by the station which are located on boarding areas, platforms or mezzanines shall provide visual characters complying with ICC A117.1 Signs covered by this provision shall, to the maximum extent practicable, be placed in uniform locations within the transit system. |
ANSI 805.6.2 Routes and Destinations. Lists of stations, routes and destinations served by the station that are located on boarding areas, platforms, or mezzanines shall have visual characters complying with Section 703.2. A minimum of one tactile sign complying with Section 703.3 shall be provided on each platform or boarding area to identify the specific station. EXCEPTION: Where sign space is limited, characters shall not be required to exceed 3 inches (76 mm) in height. |
||
810.6.3 Station Names. Stations covered by this section shall have identification signs complying with 703.5. Signs shall be clearly visible and within the sight lines of standing and sitting passengers from within the vehicle on both sides when not obstructed by another vehicle. |
10.3.1(5) Stations covered by this section shall have identification signs complying with 4.30.1, 4.30.2, 4.30.3, and 4.30.5. Signs shall be placed at frequent intervals and shall be clearly visible from within the vehicle on both sides when not obstructed by another train. When station identification signs are placed close to vehicle windows (i.e., on the side opposite from boarding) each shall have the top of the highest letter or symbol below the top of the vehicle window and the bottom of the lowest letter or symbol above the horizontal mid-line of the vehicle window. |
IBC E109.2.2.2 Identification signs. Stations covered by this section shall have identification signs containing visual characters complying with ICC A117.1. Signs shall be clearly visible and within the sightlines of a standing or sitting passenger from within the train on both sides when not obstructed by another train. |
ANSI 805.6.3 Station Names. Stations covered by this section shall have identification signs with visual characters complying with Section 703.2. The signs shall be clearly visible and within the sight lines of a standing or sitting passenger from within the vehicle on both sides when not obstructed by another vehicle. |
||
10.3.1(11) Illumination levels in the areas where signage is located shall be uniform and shall minimize glare on signs. Lighting along circulation routes shall be of a type and configuration to provide uniform illumination. |
||
810.7 Public Address Systems. Where public address systems convey audible information to the public, the same or equivalent information shall be provided in a visual format. |
10.3.1(14) Where public address systems are provided to convey information to the public in terminals, stations, or other fixed facilities, a means of conveying the same or equivalent information to persons with hearing loss or who are deaf shall be provided. |
IBC E109.2.7 Public address systems. Where public address systems convey audible information to the public, the same or equivalent information shall be provided in a visual format. |
ANSI 805.7 Public Address Systems. Where public address systems convey audible information to the public, the same or equivalent information shall be provided in a visual format. |
||
810.8 Clocks. Where clocks are provided for use by the public, the clock face shall be uncluttered so that its elements are clearly visible. Hands, numerals and digits shall contrast with the background either light-on-dark or dark-on-light. Where clocks are installed overhead, numerals and digits shall comply with 703.5. |
10.3.1(15) Where clocks are provided for use by the general public, the clock face shall be uncluttered so that its elements are clearly visible. Hands, numerals, and/or digits shall contrast with the background either light-on-dark or dark-on-light. Where clocks are mounted overhead, numerals and/or digits shall comply with 4.30.3. Clocks shall be placed in uniform locations throughout the facility and system to the maximum extent practicable. |
IBC E109.2.8 Clocks. Where clocks are provided for use by the general public, the clock face shall be uncluttered so that its elements are clearly visible. Hands, numerals and digits shall contrast with the background either light-on-dark or dark-on-light. Where clocks are mounted overhead, numerals and digits shall comply with ICC A117.1, Section 703.4. |
ANSI 805.8 Clocks. Where clocks are provided for use by the public, the clock face shall be uncluttered so that its elements are clearly visible. Hands, numerals and digits shall contrast with the background either light–on–dark or dark–on–light. Where clocks are installed overhead, numerals and digits shall be visual characters complying with Section 703.2. |
||
810.9 Escalators. Where provided, escalators shall comply with the sections 6.1.3.5.6 and 6.1.3.6.5 of ASME A17.1 (incorporated by reference, see "Referenced Standards" in Chapter 1) and shall have a clear width of 32 inches (815 mm) minimum. EXCEPTION: Existing escalators in key stations shall not be required to comply with 810.9. |
10.3.1(16) Where provided in below grade stations, escalators shall have a minimum clear width of 32 inches. At the top and bottom of each escalator run, at least two contiguous treads shall be level beyond the comb plate before the risers begin to form. All escalator treads shall be marked by a strip of clearly contrasting color, 2 inches in width, placed parallel to and on the nose of each step. The strip shall be of a material that is at least as slip resistant as the remainder of the tread. The edge of the tread shall be apparent from both ascending and descending directions. |
ANSI 805.9 Escalators. Where provided, escalators shall have a 32–inch (815 mm) minimum clear width, and shall comply with Requirements 6.1.3.5.6 – Step Demarcations, and 6.1.3.6.5 – Flat Steps of ASME A17.1 listed in Section 105.2.5. EXCEPTION: Existing escalators shall not be required to comply with Section 805.9. IBC 3005.2.2 Escalators. Where provided in below-grade transportation stations, escalators shall have a clear width of 32 inches (815 mm) minimum. Exception: The clear width is not required in existing facilities undergoing alterations. |
10.3.1(17) Where provided, elevators shall be glazed or have transparent panels to allow an unobstructed view both in to and out of the car. Elevators shall comply with 4.10. EXCEPTION: Elevator cars with a clear floor area in which a 60 inch diameter circle can be inscribed may be substituted for the minimum car dimensions of 4.10, Fig. 22. |
||
810.10 Track Crossings. Where a circulation path serving boarding platforms crosses tracks, it shall comply with 402. EXCEPTION: Openings for wheel flanges shall be permitted to be 2 1/2 inches (64 mm) maximum. |
10.3.1(13) Where it is necessary to cross tracks to reach boarding platforms, the route surface shall be level and flush with the rail top at the outer edge and between the rails, except for a maximum 2-1/2 inch gap on the inner edge of each rail to permit passage of wheel flanges. Such crossings shall comply with 4.29.5. Where gap reduction is not practicable, an above-grade or below-grade accessible route shall be provided. |
IBC E109.2.6 Track crossings. Where a circulation path serving boarding platforms crosses tracks, an accessible route complying with ICC A117.1 shall be provided. Exception: Openings for wheel flanges shall be permitted to be 2 1/2 inches (64 mm) maximum. |
ANSI 805.10 Track Crossings. Where a circulation path serving boarding platforms crosses tracks, it shall comply with Section 402. EXCEPTION: Openings for wheel flanges shall be permitted to be 2 1/2 inch (64 mm) maximum. |
||
811 Storage |
4.25 Storage. |
ANSI 905 Storage Facilities |
811.1 General. Storage shall comply with 811. |
4.25.1 General. Fixed storage facilities such as cabinets, shelves, closets, and drawers required to be accessible by 4.1 shall comply with 4.25. |
ANSI 905.1 General. Accessible storage facilities shall comply with Section 905. |
811.2 Clear Floor or Ground Space. A clear floor or ground space complying with 305 shall be provided. |
4.25.2 Clear Floor Space. A clear floor space at least 30 in by 48 in (760 mm by 1220 mm) complying with 4.2.4 that allows either a forward or parallel approach by a person using a wheelchair shall be provided at accessible storage facilities. |
ANSI 905.2 Clear Floor Space. A clear floor space complying with Section 305 shall be provided. |
811.3 Height. Storage elements shall comply with at least one of the reach ranges specified in 308. |
4.25.3 Height. Accessible storage spaces shall be within at least one of the reach ranges specified in 4.2.5 and 4.2.6 (see Fig. 5 and Fig. 6). Clothes rods or shelves shall be a maximum of 54 in (1370 mm) above the finish floor for a side approach. Where the distance from the wheelchair to the clothes rod or shelf exceeds 10 in (255 mm) (as in closets without accessible doors) the height and depth to the rod or shelf shall comply with Fig. 38(a) and Fig. 38(b). NOTE: Figure 38(a) indicates that if the clear floor space allows a parallel approach by a person in a wheelchair and the distance between the wheelchair and the shelf exceeds 10 inches, the maximum high side reach shall be 48 inches (1220 mm) above the floor and the low side reach shall be a minimum of 9 inches (230 mm) above the floor. The shelves can be adjustable. The maximum distance from the user to the shelf shall be 21 inches (535 mm). Figure 38(b) indicates that if the clear floor space allows a parallel approach by a person in a wheelchair and the distance between the wheelchair and the clothes rod exceeds 10 inches, the maximum high side reach shall be 48 inches (1220 mm). The maximum distance from the user to the clothes rod shall be 21 inches (535 mm). |
ANSI 905.3 Height. Accessible storage elements shall comply with at least one of the reach ranges specified in Section 308. |
8.4 Card Catalogs and Magazine Displays. Minimum clear aisle space at card catalogs and magazine displays shall comply with Fig. 55. Maximum reach height shall comply with 4.2, with a height of 48 in (1220 mm) preferred irrespective of approach allowed. NOTE: Figure 55 indicates the lowest shelf of a card catalog shall be 18 inches (455 mm). |
||
811.4 Operable Parts. Operable parts shall comply with 309. |
4.25.4 Hardware. Hardware for accessible storage facilities shall comply with 4.27.4. Touch latches and U-shaped pulls are acceptable. |
ANSI 905.4 Operable Parts. Operable parts of storage facilities shall comply with Section 309. |