This guide explains requirements in the ADA Standards for toilet rooms.

Notational tips for users of screen reading software follow.  In this document ″ indicates inches and ′ indicates feet.  Some images are paired with visually hidden notes.&nbsp These annotations are prefaced with begin and end image notes.

Required Compliance

[§213]

Plumbing and building codes address the number and type of toilet rooms and toilet fixtures required for a facility. The ADA Standards, on the other hand, do not address the number of toilet rooms or fixtures required for a facility, but instead specify which ones must be accessible where provided. In new construction, access is required to all toilet rooms, including those for employees. However, where single user toilet rooms are clustered in one location, at least half for each use must comply (§213.2., Ex. 4). In the case of single user portable units, access is required to at least 5% at each cluster, excluding those on construction sites for construction personnel which are fully exempt (§213.2, Ex. 3, §203.2).

Clustered Single User Toilet Rooms

Clustered single user toilet rooms (2 minimum) are those that are next to, or close to, one another. No more than 50% for each use within a cluster must comply. Compliant toilet rooms and portable units must be labeled by the International Symbol of Accessibility unless all are accessible (§213.2, Ex. 3, §216.8).

Single-user restrooms along a corridor

Unisex (Single-Use or Family) Toilet Rooms

[§213.2]

Unisex restroom symbol

Where multi-user toilet rooms are provided, accessible unisex toilet rooms cannot serve as a substitute for access to multi-user rooms, except in alterations where making multi-user rooms comply is not technically feasible (§213.2, Ex. 1). Otherwise, where multi-user and unisex restrooms are provided, both types must comply. Providing an accessible unisex toilet room in addition to multi-user toilet rooms is helpful for those who use personal care assistants of the opposite sex. The International Building Code (IBC) requires accessible unisex or "family" toilet rooms in assembly and mercantile occupancies where a total of six or more toilet fixtures is required (§1108.2.1 in the 2000 IBC and §1109.2.1 in later editions). The ADA Standards require that unisex toilet rooms, where provided, have privacy latches and contain at most one lavatory, one water closet, and one urinal (or a second water closet) (§213.2.1).

Medical Care and Long-Term Care Facilities

[§223.1]

medical care icon

In licensed medical care and long-term care facilities, toilet rooms that are part of accessible patient or resident sleeping rooms, excluding critical or intensive care patient sleeping rooms, must comply (§223.1, Ex., §805.4). The Standards cover independent accessibility and do not address design for use that is assisted by medical or resident care personnel. Features for assisted use that conflict with the Standards can be provided in those toilet rooms serving rooms not required to comply with the Standards. Otherwise any departure from the Standards must be based on the provision for “equivalent facilitation” (§103) which permits alternatives to specified requirements that provide substantially equivalent or greater accessibility and usability. This means that the alternative solution is just as, if not more, effective than what is required by the Standards in terms of accessibility, usability, convenience, and reliability for people with disabilities.

Toilet Room Location

The Standards specify the location of toilet rooms in two instances:

  • Where toilet rooms are provided in multi-story facilities that are exempt from the requirement for vertical access between stories (§F206.2.3, Ex. 1 or 2), a toilet room must be provided on a story that is connected to an accessible entrance by an accessible route (§F213.1). Toilet rooms on other stories must fully comply as well.
  • In alterations where it is technically infeasible to make men’s and women’s rooms comply, an accessible unisex toilet room is permitted as an alternative if it is located in the same area and on the same floor as the existing toilet rooms (§F213.2, Ex. 1).

Additions

[§202.2]

Additions are required to comply with requirements in the Standards for new construction. Each toilet room of an addition must comply as would be required in new construction.

Alterations

[§202.3]

When existing toilet rooms are altered, the Standards apply according to the planned scope of work. If one toilet room on a floor is altered, the Standards apply to that room only; if all toilet rooms on a floor are altered, the Standards apply to each toilet room that would be required to comply in new construction. The scope of work also determines which technical requirements apply. If some, but not all, elements in a toilet room are altered, only those elements altered must comply. If a room or space is completely altered (or built new as part of an alteration), the entire room or space must comply.

Restroom with water closet and mirror above lavatory highlighted

In a project involving alterations to the toilet, grab bars, faucet controls, and mirror in a restroom, the Standards apply to these elements but not to those that remain unaltered. In more extensive projects where additional elements are altered, application of the Standards is greater, commensurate with the scope of work.

Compliance in an alteration is not required where it is "technically infeasible." The term is defined as "something that has little likelihood of being accomplished because existing structural conditions would require removing or altering a load-bearing member that is an essential part of the structural frame; or because other existing physical or site constraints prohibit modification or addition of elements, spaces, or features that are in full and strict compliance with the minimum requirements." For example, combining two toilet compartments to create an accessible compartment may be technically infeasible where it would reduce the fixture count below the number required by the applicable plumbing code.

When it is technically infeasible to make existing men's and women's rooms comply, an accessible unisex toilet room can be provided instead if it is in the same area and on the same floor as the existing toilet rooms (§213.2, Ex. 1). Where technical infeasibility is encountered, compliance is still required to the maximum extent feasible.

Alterations and Additions to Primary Function Areas

[§202.4]

When an area containing a primary function (a major activity intended for a facility) is altered or added to a facility, an "accessible path of travel" is required. The accessible path of travel, which must extend from site arrival points to the primary function area, includes provided restrooms (at least one for each sex or, if only unisex restrooms are provided, at least one unisex restroom), telephones, and drinking fountains, where provided, that serve the primary function area. The accessible path of travel is required to the extent that it does not cost more than 20% of the total cost of the work to the primary function area. Compliance is required up to the point this cost cap is reached, even where it does not result in a fully accessible path of travel. See the Alterations and Additions Guide.

Alterations to Qualified Historic Facilities

[§202.5]

historic site

The Standards provide certain exceptions for qualified historic facilities where compliance in an alteration would threaten or destroy the historic integrity or significance of a facility as determined by the appropriate State Historic Preservation Official or Advisory Council on Historic Preservation. One of these exceptions allows access to be provided to a unisex toilet room or to one men's and one women's room regardless of the number of toilet rooms altered or added (§213.2, Ex. 2).

This guide notes some provisions in the International Building Code (IBC) and the ICC A117.1 Standards for Accessible and Usable Buildings and Facilities that are not found in the ADA Standards. For example, the A117.1 standard, which provides technical provisions and is referenced by the IBC, requires a vertical grab bar at water closets. Not all differences between the ADA Standards and editions of the IBC and A117.1 standard are noted in this guide.

Components of Accessible Single User Toilet Room

Requirements in the Standards for toilet rooms address doors, turning space, plumbing fixtures, mirrors, dispensers, shelves, and other elements provided.Other provisions in the Standards also apply.

Single-user toilet room with elements noted: Water Closet (§213.3.2),
Toilet Paper Dispenser (§604.7), Lavatory (§213.3.4) where provided,
Mirror (§213.3.5) where provided, Coat Hooks and Shelves (§213.3.7) at
least 1 of each type where provided, Dispensers and Receptacles (§205)
where provided, Turning Space (§603.2.1) 60 inches diameter circle or
T-turn.

Urinals (§213.3.3)

urinal
An accessible urinal is required only in toilet rooms where more than one urinal is provided.

Water Closets

[§213.3.2, §604]

Criteria for water closets address location, clearance, seats, grab bars, flush controls, and dispensers. Water closets can be arranged for either a left-hand or right-hand approach.

Location, Clearance, Seat Height and Flush Controls

Water closet (plan view) with centerline 16 inches to 18 inches from side wall and clearance 60 inches wide minimum by 56 inches deep minimum. Note: specifying 17 inches will accommodate construction variations up to 1 inch
The required clearance provides space for approach and transfer to water closets. The water closet, associated grab bars, toilet paper dispensers, seat cover and other dispensers, coat hooks, shelves, and sanitary napkin disposal units are the only elements that can overlap this clearance (§604.3.2). Other elements and fixtures cannot overlap the required water closet clearance. (In residential dwelling units, a lavatory can overlap a portion of the water closet clearance under certain conditions.)

Water closet (elevation) with seat 17 inches 19 inches high measured to the top
of the seat. Notes: Flush controls must be on the open side and, if
hand-operated, comply as operable parts). Seats cannot be sprung to
return to lifted
position.

Grab Bars

[§604.5]

Grab bars are required to be mounted on the walls beside and behind the water closet. They can be separate or continuous. When returned to walls, the length is measured to the centerline of the return, consistent with industry practice. When attached at other points along the bar, the length is measured to the end of the bar.

Rear Grab Bar Water closet (elevation) with rear grab bar 36 inches long minimum that extends 12 inches minimum on one side of the water closet centerline and 24 inches on the other side; grab bar is 33 inches to 36 inches high measured to the top of the gripping surface.
Side Grab Bar Water closet (elevation) with side grab bar 42 long minimum that is 12 inches maximum from the rear wall and extends 54 inches minimum in front of the water closet; the grab bar is 33 inches to 36 inches high measured to the top of the gripping surface.
The rear grab bar can be shifted to the open side of the water closet or split where it would conflict with the location of flush controls required by applicable codes (§604.5.2).
Water closet with rear grab bar that is split because of the location of flush
controls Water closet with grab bar shifted to open side to not conflict with
location of flush control

Grab bars and wall or other surfaces adjacent to them must be free of abrasive or sharp elements. Any projecting object must be located at least 12″ above grab bars and at least 1½″ from the bottom and ends of grab bars so that the reach and use of grab bars is not impeded.

Minimum Clearances at Grab Bars

Clearance at side grab bar shown to extend 12 inches minimum above the bar and 1 1/2 inches minimum from the ends and bottom of the bar
Hand shown gripping side grab bar

Grab bars can have circular or non-circular cross-sections but must have rounded edges. The 1½″ clearance between the grab bar and wall is not a minimum but an absolute dimension to prevent entrapment. Grab bars cannot rotate within fittings. The structural strength of grab bars must withstand a vertical or horizontal force of 250 lbs. at any point on the grab bar, fastener, mounting device, or supporting structure.

Cross Section and Clearance

Grab bar with a circular cross section 1 1/4 inches to 2 inches in diameter and a clearance from the wall 1 1/2 inches
Grab bar with non-circular cross section with rounded edges and a perimeter dimension 4 inches to 4.8 inhces, a maximum cross-section dimension of 2 inches, and a clearance 1 1/2 inches from the wall

The Standards do not require or address additional folding or swing-away grab bars on the open side of the water closet. However, if provided, they must be mounted so that they do not interfere with use of the required grab bars or the clear floor space at water closets. Also, it is important they are properly secured (although this is not addressed by the Standards).

Vertical Grab Bar (ICC A117.1 Standard) The ICC A117.1 Standard for Accessible and Usable Buildings and Facilities, which is referenced by the International Building Code, requires an 18″ minimum vertical grab bar at water closets. The ADA Standards do not require this grab bar but allow a second grab bar to be within the 12″ clearance above the horizontal grab bar (§609.3) if there is a separation of 1½″ minimum
water closet with vertical grab bar above the horizontal side grab bar

Toilet Paper Dispensers

[§604.7]

toilet paper
dispenser

Toilet paper dispensers must be within accessible reach from the water closet. They can be located below or above (but not behind) grab bars, though it is important that non-recessed dispensers be outside the 12″ minimum high clearance above the bar yet not exceed the 48″ maximum height (measured to the outlet) of the dispenser. Dispensers must allow continuous paper flow and cannot control delivery.

large two-roll toilet paper dispenser

Recessed Dispenser Location

Recessed toilet paper dispenser location 15 inches to 48 inches above the floor
(measured to dispenser outlet) and dispenser centerline 7 inches to 9 inches beyond
leading edge of water closet

Non-Recessed Dispenser Location

Non-recessed toilet paper dispenser location 15 inches minimum high and 1
1/2 inches minimum below the grab bar and 12 inches minimum above the grab bar and 48 inches
high, measured to the outlet; centerline 7 inches to 9 inches beyond leading edge
of water closet

If the grab bar is 36″ high, a non-recessed toilet paper dispenser located above the bar must have an outlet at exactly 48″ high to accommodate both the maximum reach height and the 12″ minimum clearance above the grab bar.

Example Single User Toilet Room

The Standards do not directly specify the size of toilet rooms which is determined by a variety of factors, including the layout and number of fixtures, the presence of other features, such as baby changing tables, and even the swing of doors. How various space requirements are met also determine the minimum room size, including required clearances at fixtures and other elements, turning space, and door maneuvering clearance.

Accessible toilet rooms can be configured in many different ways. The layout shown here is used only as an example in illustrating the features of a compliant toilet room. These designs show the minimum dimensions specified in the Standards. Providing additional space in toilet rooms will enhance usability.

Water Closet Clearance Water closet in corner with clearance 60 inches wide minimum and 56 inches minimum deep Water closets can be placed in any corner.
Lavatory Clearance Water closet with lavatory next to it. Lavatory has clear floor space 30 inches minimum by 48 inches for a forward approach. The lavatory does not overlap the water closet clearance, but a portion of the lavatory clearance does. The lavatory cannot overlap the water closet clearance (except in residential dwelling units), but the clearance at the lavatory can. It is advisable (but not required) to nominally center the lavatory on the clear floor space.

Option: Recessed Lavatory

Lavatory recessed next to water closet to be located outside the water closet clearance. Rear grab bar at water closet 24 inches If a lavatory or other fixture is recessed next to a water closet, the rear grab bar can be 24″ (instead of 36″) long minimum, centered on the unit if wall space does not allow a grab bar 36″ long minimum (§604.5.2).
Two single-user toilet rooms located back-to-back with recessed lavatories next to the water closet. Recessed fixtures can save space where two rooms are paired.

Doors

[§404]

Maneuvering clearance is required at doors based on the approach and swing. No elements can overlap door maneuvering clearances.

Push-Side Maneuvering Clearance Toilet room with a water closet and an adjacent lavatory. A door opposite the lavatory swings out. The door maneuvering clearance is 48 inches deep and abuts the lavatory. A strike-side clearance 12 inches minimum on the latch side of the door is required if the door has both a closer and a latch.
Pull-Side Maneuvering Clearance Toilet room with a water closet and an adjacent lavatory. A door opposite the lavatory swings in. The door maneuvering clearance is 60 inches deep and abuts the lavatory. A strike-side clearance 18 inches minimum is required on the latch side of the door.

Doors can swing into fixture clearances in single-user toilet rooms where unobstructed wheelchair space is available beyond the door swing (603.2.3). This provides space to enter the room and clear the door using wheeled mobility aids.

Door Swing Outside Fixture Clearances Toilet room with a water closet and an adjacent lavatory with a door opposite the lavatory that swings in. The door does not swing into the clearances at the water closet and lavatory.
Wheelchair Space Beyond Door Swing Toilet room with a water closet and an adjacent lavatory with a door opposite the lavatory that swings in. A clear floor space 30 inches minimum by 48 inches minimum that provides space for an occupied wheelchair is unobstructed and located beyond the swing of the door. The location and orientation of the wheelchair space is not specified, but it should be easy to access upon entry into the room.

Turning Space

[§304]

Turning space is required in the room and can be provided as a 60″ diameter circle or T-shaped space. Doors can swing into the turning space. The orientation of the T-shaped space is not specified, and it can be located for approach at any segment (i.e., the stem or either arm).

Circular Turning Space Toilet room with a water closet, an adjacent lavatory, and turning space in the form of a 60 inches minimum diameter circle.
T-Shaped Turning Space Toilet room with a water closet, an adjacent lavatory, and turning space in the form of a T-shaped space. Each arm of the T is 36 inches wide minimum and the center stem extends 24 inches minimum from perpendicular segment which is 60 inches long minimum The location and orientation of the wheelchair space is not specified, but it should be easy to access upon entry into the room.

Elements with knee and toe clearance can overlap a portion of the turning space. With t-shaped space, overlap is limited to one segment of the “T” so that the other two remain clear for approach and backing up.

Lavatory with knee and toe space shown overlapping a portion of the turning circle.
Lavatory with knee and toe space shown overlapping only one segment of the T-shaped turning space. This overlap is limited to one segment so that the other two segments of the T are clear for approach and backing up.

Approximate Room Dimensions

With a water closet and lavatory side-by-side, the plumbing wall is typically determined by the width of the water closet clearance, the lavatory fixture width, plus any additional lavatory clearance beyond the fixture (unless the lavatory is recessed). Other elements provided, such as a baby changing table, may increase this dimension.

Toilet room with a water closet and an adjacent lavatory with a door
opposite the lavatory that swings in. The width of the room is based on:
the 60 inches minimum wide water closet clearance, the lavatory width, and half
the lavatory clearance width not overlapped by the lavatory (if it is
centered on the fixture).

In the same example, if the door is opposite the plumbing wall and swings in, the room depth will likely be determined by keeping the door swing outside fixture clearances (left). Alternatively, if there is unobstructed wheelchair space beyond the door swing, the door maneuvering clearance and the horizontal depth of the lavatory may determine the room depth (right). Turning space is typically available in the room without further increase in room size where doors swing in.

Figure: Toilet room with a water closet and an adjacent lavatory with
a door opposite the lavatory that swings in. The depth of the room is
based on the door swing clearing the water closet and lavatory
clearances. Figure: Toilet room with a water closet and an adjacent
lavatory with a door opposite the lavatory that swings in. Unobstructed
wheelchair space is provided beyond the swing of the door. The depth of
the room is based on the 60 inches depth of the door maneuvering clearance and
the horizontal depth of the lavatory which abuts, but does not overlap,
the door maneuvering
clearance.

Note: Other elements provided may increase minimum room dimensions.

If the door swings out, the room depth is usually determined by the door maneuvering clearance and the horizontal depth of the lavatory. Turning space usually can be provided without further increase in this design but providing additional depth will help minimize fixture overlap of the turning space for improved access.

Note: Other elements provided may increase minimum room dimensions.

Toilet room with a water closet and an adjacent lavatory. A door
opposite the lavatory swings out. The depth of the room is based on the
48 inches depth of the door maneuvering clearance and the horizontal depth of
the lavatory which abuts, but does not overlap, the door maneuvering
clearance. Turning space overlaps the door clearance, and a portion is
overlapped by the lavatory. Note: Other elements provided may increase
minimum room dimensions.

Example: Lavatory Opposite Water Closet

Toilet rooms can be configured in many different ways, but the same requirements apply, including those for fixtures, doors, and turning space. This example shows a door swing located outside fixture clearances (obviating the need for wheelchair space beyond the arc of the door swing) and turning space free of any overlapping elements (left). Fixtures and other elements can overlap turning space but not the door maneuvering clearance (right).

Toilet room with a water closet in a back corner and a lavatory on the front wall opposite the toilet. The water closet and lavatory clearances partly overlap. The door is located next to the lavatory and swings in. It swings into turning circle which overlaps a portion of the fixture clearances.
Toilet room with a water closet in a back corner and a lavatory on the front wall opposite the toilet. The door is located next to the lavatory and swings in. The lavatory does not overlap the door maneuvering clearance.

Dispensers and Receptacles [§205, §309], Coat Hooks and Shelves [§213.3.7, §603.4]

[§205]

Dispensers, receptacles, and other operable parts, as well as shelves and coat hooks, must comply where provided.

Person using a wheelchair at a paper towel dispenser with a
receptacle. Clear floor space at the dispenser is highlighted. Notes:
Dispensers & Receptacles (§205, §309), Hand-operated soap dispensers
that are fixed, paper towel dispensers, toilet seat cover dispensers,
and other types of dispensers provided must comply as operable parts, as
well as trash receptacles and other receptacles. Operable Parts (§309),
Operable parts must have compliant clear floor space for a forward or
side approach. They also must be located within accessible reach range
and usable with one hand and without tight grasping, pinching, twisting
of the wrist, or more than 5 pounds force. Coat Hooks (§213.3.7, §603.4)
If coat hooks are provided, at least one must be within accessible reach
range. Shelves (§213.3.7, §603.4) If shelves are provided, at least one
of each type must be located 40 inches minimum to 48 inches maximum AFF.

Baby Changing Tables

[§226]

baby changing icon

Where baby changing tables are provided, they must comply as a work surface and, if they project into circulation paths, as protruding objects.

Wall-mounted baby-changing table in a toilet room. Table surface is
28 inches to 34 high and must comply as a work surface (§902) and clear floor
space for a forward approach to the table is shown. When stowed, the
table projection from the wall is limited to 4 inches maximum if the leading edge
is higher than 27." Notes: Compliant as protruding object (when stowed)
if it protrudes into a circulation path (§204, §307); Compliant operable
parts (§205,
§309).

Toilet room with water closet and adjacent lavatory and a baby-changing table on the opposite wall. The table does not overlap fixture clearances or the door maneuvering clearance when stowed Baby changing tables cannot overlap fixture clearances or door maneuvering clearances when stowed.
Toilet room with water closet and adjacent lavatory and a baby-changing table on the opposite wall. Clear floor space for a forward approach is shown at the table in the down position. Clear space for a forward approach to the table is required. This space can overlap fixture clearances and door maneuvering clearances.

Private Toilet Rooms Accessed through a Private Office

Single-occupant toilet rooms accessed only through a private office and not for common or public use are permitted exceptions that allow certain access features, such as grab bars, to be provided after construction as needed. However, they still must be sized for accessibility and fully meet all space requirements. Enlarging or reconfiguring a private toilet room is not permitted by the Standards as a post-construction accommodation.

Exceptions for Private Toilet Rooms

Note: All other applicable requirements, including clearances and turning space, must be met.

Private toilet room with water closet and lavatory. Notes: Grab bars
can be installed after construction if walls are properly reinforced/
blocked (§604.5, Ex. 1) Toilet seat height not required to comply
(§604.4, Ex. 1) Lavatory height not required to comply knee and toe
space below is not required but must be made available when needed
(§606.2, Ex. 2, §606.3, Ex. 1)) Door can swing into fixture clearances
if the swing can be reversed and fully comply with §404 or if
unobstructed wheelchair space is provided in the room beyond the arc of
the door swing (§603.2.3, Ex. 1 and
2).

Water Closets in Residential Dwelling Units

In residential dwelling units required to be mobility accessible, at least one bathroom must comply (§809.4). Accessible water closets in dwelling units are permitted several exceptions that allow some features, such as grab bars and knee and toe space below lavatories, to be provided after construction as needed if certain conditions are met. In addition, lavatories can overlap a portion of the water closet clearance if additional clearance depth is provided.

Exceptions for Water Closets in Dwelling Units

Note: All other applicable requirements, including clearances and turning space, must be met.

Dwelling unit toilet room with a water closet with a 15 inches to 19 inches seat
height and lavatory with base cabinetry. Notes: Toilet Seat Height - A
lower toilet seat height is permitted (§604.4, Ex. 2). Grab Bars Grab
bars can be installed after construction if walls are properly
reinforced/ blocked (§604.5, Ex. 2). Lavatory Knee & Toe Space Cabinetry
is permitted under lavatories if: it can be taken out without removal or
replacement of the fixture, the finish floor extends beneath it, and the
walls behind and surrounding the cabinetry are finished (§606.2, Ex.
3).

Plan view of water closet and adjacent lavatory. The lavatory is 18 inches minimum from the water closet centerline and overlaps a portion of the water closet clearance which is 66 inches deep minimum
A compliant lavatory is permitted on the rear wall 18″ minimum from the water closet centerline if the clearance at the water closet is at least 66″ (instead of 56″) deep (§604.3.2, Ex.).

Dwelling Unit Water Closet and Lavatory

Water closet and adjacent lavatory shown in elevation. The rear grab
bar at the water closet extends from the water closet centerline 12 inches on
one side to the side wall and 24 inches minimum on the other side toward the
lavatory; the grab bar does not overlap the lavatory.

Water Closets and Toilet Compartments for Children’s Use

[§604.1]

Specifications based on children's dimensions can be followed when water closets and toilet compartments are designed primarily for use by children ages 12 and younger. Structured as exceptions, these provisions are optional and serve as alternatives to adult-based dimensions. Under the Standards, the decision to design a toilet room for children is left to other building requirements or regulations, good practice, client preference, or other factors. When a toilet room or compartment is designed for children, all pertinent alternate specifications for toilets, compartments, grab bars, and dispensers must be applied.

The Standards provide non-mandatory guidance on specifications according to the age group served that reflect the differences in size, stature, and reach ranges of children ages 3 through 12. The chosen specifications should correspond to the primary user group and be consistent within an age bracket. If the planned user group spans more than one age group, one can select specifications that align on the borderline between the two groups.

Water Closet for Children 12 and Younger

Note: All other requirements for children's water closets and toilet compartments are consistent with those based on adult dimensions.

Children’s water closet with: the centerline 12 inches to 18 inches from the side wall, a seat height 11 inches to 17 inches, a rear grab bar 18 inches to 27 inches high, and flush controls 36 inches maximum high. Water closet centerline, seat height, and grab bar height
Children’s water closet shown from the side with a side grab bar 18 inches to 27 inches high and a toilet paper dispenser height 14 inches minimum to 19 inches maximum Grab bar and toilet paper dispenser height

The rear grab bar can be shifted to the open side of the water closet or split where it would conflict with the location of flush controls required by the applicable code (§604.5.2, Ex. 2).

Advisory (Non-Mandatory) Specifications by Age Group
3 & 4 5 through 8 9 through 12
Water Closet Centerline 12″ 12″ to 15″ 15″ to 18″
Toilet Seat Height 11″ to 12″ 12″ to 15″ 15″ to 17″
Grab Bar Height 18″ to 20″ 20″ to 25″ 25″ to 27″
Dispenser Height 14″ 14″ to 17″ 17″ to 19″

Portable Toilet Units

Where portable single user toilet units are provided, including at temporary events, access is required to at least 5% in each cluster (213.2, Ex. 3). Compliant units must be labeled by the International Symbol of Accessibility (ISA). Portable units must meet all requirements for toilet rooms that apply, including fixture clearances, turning space, and door maneuvering clearances.

An accessible route and entrance are required to serve portable units. Ramps necessary for changes in level must fully comply, and entrance landings must be sized to accommodate door maneuvering clearances and ramp landings.
Portable toilet with ramp to entrance and labelled by the ISA
Plan view of portable toilet with water closet in corner with side and rear grab bars; water closet clearance and turning space highlighted.
Compliance with all other applicable provisions for water closets, including those for grab bars and clearance, is required. Other requirements for toilet rooms, such as door maneuvering clearance (not shown) and turning space also apply.

Multi-User Toilet Rooms

The Standards address toilet compartments and urinals which apply in addition to criteria for toilets, lavatories, mirrors, dispensers, shelves, and other elements provided.

Components of Multi-User Toilet Rooms

Multi-user men's room with toilet compartments, urinals, lavatories.
Notes: At least one wheelchair accessible toilet compartment (§213.3.1)
At least one compliant urinal where more than one urinal is provided
(§213.3.3) At least one compliant lavatory (not located in a toilet
compartment) and at least one compliant mirror, where provided (§213.3.4
and §213.3.5) At least one ambulatory accessible toilet compartment in
restrooms with at least 6 toilet compartments or where the combined
total of toilets and urinals is at least 6 fixtures (§213.3.1)
Dispensers, receptacles, and other operable parts must comply where
provided (§205) turning space (§603.2.1)

Detail of multi-user toilet room shows door not swinging into lavatory
clearance. Note: Doors, including toilet compartment doors, cannot swing
into the clear floor space required at plumbing fixtures (§603.2.3), but
they can swing into turning space.

Wheelchair Accessible Toilet Compartments

[§213.3.1]

At least one toilet compartment must be wheelchair accessible where toilet compartments are provided.

Coat Hook - note: Compliant coat hooks and shelves where they are
provided in other toilet compartments (§213.3.7, 604.8.3). Wheelchair
accessible toilet compartment with toe clearance below the front
partition and one side partition. Notes: Compliant water closet with
additional clear floor space required if fixture is floor mounted (59 inches
instead of 56 inches deep) (§604.8.1.1). Toe clearance below the front and one
side partition unless the compartment is enlarged to include toe space
(§604.8.1.4) (partition vertical supports are permitted within this
clearance)

Wheelchair accessible toilet compartment with door in the side
partition farther from the water closet with the opening
4

Compartment doors must be offset from the water closet in either the front or the side partition so that there is space to enter the compartment. Doors can be hinged on the left or right side of the opening.

Compartment Doors

[§404]

Compartment doors must meet applicable requirements for doors, including the clear width (32″ minimum), hardware, and opening force (5 lbs. maximum).

Toilet compartment with out-swinging door. Note: Doors cannot swing
into the minimum compartment area specified. Detail of compartment door
with pull on both sides on latch side. Notes: Door must be self-closing
(gravity or spring hinges are typically used). The minimum closing time for
spring hinges is 1.5 seconds measured from a 70 degrees open position to the
closed position. Door pulls are required on both sides near the latch,
34 inches to 48 inches above the finish floor.

Compartment doors must meet maneuvering clearance requirements, but a reduced clearance is specified for compartment doors providing a latch approach. Doors can be hinged on either side.

Latch Approach Clearance Wheelchair accessible toilet compartment door with latch-approach maneuvering clearance that is 42 inch deep minimum with strike-side clearance 24 inch minimum
Forward Approach Clearance Wheelchair accessible toilet compartment door with forward-approach maneuvering clearance that is 60 inches deep minimum with strike-side clearance 18 inches minimum
Hinge Approach Clearance Wheelchair accessible toilet compartment door with hinge-approach maneuvering clearance that is 60 inches deep minimum with strike-side clearance 36 inches minimum
Alternative Hinge Approach Clearance Wheelchair accessible toilet compartment door with hinge-approach maneuvering clearance that is 54 inches deep minimum with strike-side clearance 42 inches minimum

The required size of compartments provides the minimum space needed to enter, approach and transfer to water closets, and exit. As with water closets generally, the only elements that can overlap the minimum compartment/water closet clearance are: the water closet, associated grab bars, dispensers, coat hooks, shelves, and sanitary napkin disposal units. Other elements and fixtures, including baby changing tables in the stowed position, cannot overlap this clearance. If an additional plumbing fixture, such as a lavatory, is provided in a compartment, the compartment must meet the requirements for single-user toilet rooms in §603.

Toilet compartments are typically enclosed by partitions. Full-height partitions and door assemblies are not prohibited but will require a larger compartment because toe clearance below partitions is not available.

Compartment with Toe Clearance Below Partitions

Toe clearance below partition that is 9 inches high minimum and 6 inches deep minimum
Figure: Wheelchair accessible toilet compartment with toe clearance
below partitions. Compartment is 60 inches wide minimum and 56 inches deep minimum
(wall-mounted water closet) or 59 inches deep minimum (floor-mounted water
closet). Figure: Wheelchair accessible toilet compartment without toe
clearance below partitions. Compartment is 66 inches wide minimum if there is no
toe clearance below a side partition. If there is no toe clearance below
the front partition, the depth is 62 inches minimum (wall-mounted water closet)
or 65 inches minimum (floor-mounted water closet).

Toilet Compartments Designed for Children’s Use

[§604.8.1]

Wheelchair accessible toilet compartment for children that is 60 inches wide
minimum (66 inches minimum if there is no toe clearance below a side partition. The
depth is 59 inches minimum (65 inches minimum if there is no toe clearance below the front
partition.

Toilet compartments designed for use by children 12 and younger must be slightly larger (59″ wide for wall- or floor-mounted water closets) because children's maneuvering skills are generally less refined. The toe clearance must be at least 12″ high to accommodate footrests that are higher above the floor. As with adult-sized compartments, additional space is required if toe clearance is not available below partitions.

End-of-Row Toilet Compartment

Wheelchair accessible toilet compartments located at the end of the row can provide more room by incorporating dead-end aisle space. The door can swing in if it clears the minimum compartment area. The compartment door can be located in the side partition that is closer to the water closet when the door opening is beyond the minimum depth of the compartment area.

Wheelchair accessible toilet compartment at the end of a row of
compartments with an in-swinging door that clears the minimum
compartment area.

Toilet Compartment with a Lavatory

[§603]

No other fixture besides the toilet can be located in the minimum space required for the compartment. If a lavatory or another plumbing fixture is located in a compartment, the compartment must meet requirements for toilet rooms, including turning space. Another compliant lavatory is required outside the compartment.

Wheelchair accessible toilet compartment with a lavatory next to the
water closet; fixture clearances and overlapping turning space shown
within the compartment. Notes: Door cannot swing into fixture clearances
(unless unobstructed wheelchair space beyond the door swing is provided
in the compartment (§603.2.3), Turning space required within compartment
(§603.2.1), Another compliant lavatory is required outside the
compartment (§213.3.4).

Ambulatory Accessible Toilet Compartment

[§213.3.1]

Ambulatory accessible toilet compartments provide parallel grab bars and benefit people who use crutches, canes, walkers and similar devices or who need support in sitting or standing. They do not accommodate wheelchairs or scooters and are required in addition to the wheelchair accessible compartment in toilet rooms with six or more toilet compartments or where the combined total of toilets and urinals is six or more. They are sized so that both grab bars are within reach. Grab bars must meet specifications for size, location, and securement.

Man standing in ambulatory accessible toilet compartment and gripping
both parallel grab bars. Figure: Ambulatory accessible compartment that
is 35 inches to 37 inches minimum wide and 60 inches minimum deep. Water closet centerline is
17 inches to 19 inches from side partition. Grab bars are provided on both sides and
must be 12 inches maximum from the back wall, 42 inches long minimum and extend 54 inches minimum
to the front of the compartment.

Water closet in ambulatory accessible compartment with a seat height
17 inches to 19 inches and grab bars that are 33 inches to 36 inches high measured to the top of
the gripping surface. Note: Water closets must comply, including flush
controls which must meet criteria for operable parts if hand-operated.
Seats cannot be sprung to return to lifted position. Requirements for
toilet paper dispensers, coat hooks, and shelves also apply.

Urinals

[§213.3.3]

At least one urinal must comply where two or more urinals are provided in a toilet room. Specifications address rim height, depth, flush controls, and clear floor space. Accessible urinals must be either wall hung or stall type. Flush controls must be automatic or, if hand operated, compliant as operable parts and located within accessible reach range (§309).

Wall Hung Urinal Wall-hung urinal that is 13½ inches deep minimum measured from the face of the urinal rim to the back of the fixture. The rim is 17 inches high maximum
Stall Type Urinal Stall-type urinal shown extending to floor.

Clear floor space for a forward approach is required. Partitions or privacy panels cannot obstruct or reduce the minimum clearance. If partitions or panels obstruct both sides of the clear floor space for more than 24″, the clear floor space must be at least 36″ wide instead of 30″ wide.

Clear floor space for a forward approach to a urinal shown in plan
view. Side partitions do not overlap clear floor space. The clear floor
is 48 inches minimum deep and 30 inches minimum wide (36 inches minimum wide if the partitions
obstruct the clear floor space on both sides for more than 24 inches).
Portions of wall hung urinals that provide toe clearance 9 inches high minimum
can overlap the clear floor space for a depth of 6 inches
maximum

Toilet Room Signs

[§216]

men's room sign women's room sign

Where provided, signs that identify permanent rooms and spaces, including toilet rooms, must have raised characters and braille and meet criteria for visual access (§216.2). Visual content and tactile content can be provided on separate signs.

If pictograms are provided to identify toilet rooms (i.e., symbols for men’s, women’s, and unisex restrooms), they must be on a field at least 6″ high, include the verbal equivalent below in raised characters and braille, and meet finish and contrast specifications (§703.6). These pictogram requirements do not apply to any informational pictograms that are also provided on the sign, including the International Symbol of Accessibility (ISA). If not all toilet rooms are accessible, those that comply must be labelled by the ISA. The ISA can be included on the toilet room sign or be provided separately.

restroom sign with arrow and ISA

Where existing toilet rooms in an alteration do not comply, signs with the ISA must be provided indicating the location of the nearest accessible toilet room, and those that comply must be labeled by the ISA as well (§216.8). The content of directional signs is not specified.

Common Questions

question mark

Toilet Rooms

Are toilet rooms that serve employees but not the public required to comply?

Yes. Public and common use toilet rooms, including those used exclusively by employees, must comply. Private toilet rooms for a single occupant accessed only through a private office are permitted limited exceptions for certain access features, such as the later installation of grab bars if walls have blocking or are reinforced.

Can access be provided to a unisex restroom instead of to men’s and women’s rooms?

If men’s and women’s rooms are provided, they must be accessible even if a unisex toilet room is also provided. However, in alterations when it is technically infeasible to make existing men’s and women’s rooms comply, an accessible unisex toilet room can be provided instead if it is located on the same floor and in the same area as the men’s and women’s rooms (§213.2, Ex. 1).

Is access required to a unisex family or gender-neutral toilet room that is provided in addition to accessible men’s and women’s rooms?

Yes. Unisex toilet rooms must be accessible, including where they are provided in addition to multi-user toilet rooms. Where multiple single-user toilet rooms are clustered at one location, no more than half for each use are required to comply (§213.2, Ex. 4).

How does the exception for clustered single user toilet rooms of the same type (no more than 50% at each cluster) apply when there is an odd number of toilet rooms?

When there is an odd number of single user toilet rooms of the same type in a cluster, the number of accessible toilet rooms can be rounded up or down. Rounding up is recommended for better access and is otherwise required when fractions or remainders result in determining the number of facilities or elements required to comply (§104.2). However, rounding down is permitted in this instance because the exception for clustered single user toilet rooms states that “no more than 50 percent of the single user toilet rooms for each use at each cluster shall be required to comply” (§213.2, Ex. 4).

Is there a maximum distance or separation that applies to toilet rooms within the same cluster?

No maximum distance is specified, but clustered single user toilet rooms are those that are next to, or close to, one another.

What is the impact of providing two unisex toilet rooms instead of a designated single-user men’s room and a designated single-user women’s room?

If two unisex restrooms of the same type are clustered in one location, only one of the two is required to comply under the Standards (§213.2). If a single-user men's room and a single-user women's room are provided, both must comply even if clustered since they are different types.

Can toilet rooms be designed for assisted instead of independent access?

The Standards address independent accessibility and do not contain requirements for spaces and elements designed for assisted use. In medical care facilities, features for assisted use that conflict with the Standards can be provided in those toilet or bathing rooms serving patient bedrooms that are not required to comply with the Standards. Otherwise, any departure from the Standards, including those related to assisted use, must be based on the provision for "equivalent facilitation" (§103) which permits alternatives to specified requirements that provide substantially equivalent or greater accessibility and usability.

In facilities that are exempt from the requirement for vertical access between stories, are toilet rooms required to comply on stories not connected by an accessible route?

Yes. In facilities that are not required to provide an accessible route between stories based on the story count or square footage per floor (§206.2.3, Ex. 1 or 2), all other provisions in the Standards, including those for toilet rooms, still apply to levels and stories not connected by an accessible route. In addition, if a toilet room is provided on an inaccessible story of such a facility, a toilet room also must be provided on an accessible story so that it is connected to an accessible entrance by an accessible route (§213.1).

What is the minimum size of toilet rooms?

The standards do not specify the minimum size of toilet rooms. The required size of a toilet room is determined by room layout, the number and configuration of fixtures provided, required clearances, the presence of baby changing tables and other amenities, turning space, door maneuvering clearances, and other factors and requirements.

Can doors swing into the turning space and fixture clearances?

Doors can swing into the turning space. They cannot swing into the clearance required at plumbing fixtures, except in single user toilet rooms where clear floor space 30″ minimum by 48″ minimum is provided in the room beyond the arc of the door swing (§603.2.3, Ex. 2). In addition, doors can swing into fixture clearances at single-occupant toilet rooms accessed only through a private office and not for common use if the swing of the door can be reversed (§603.2.3, Ex. 1).

When is a toilet room required to be designed for children?

The Standards do not require that toilet rooms be designed for children. This determination is usually made based on other building requirements or regulations, good practice, or client preference. However, the Standards do provide alternate specifications based on children's dimensions that can be followed where a toilet room is designed for children.

If a restroom serves both adults and children, must an accessible toilet compartment be provided for both adults and children?

In restrooms that serve both adults and children, it is advisable, but not required, to provide wheelchair accessible toilet compartments for both user groups, but the Standards require only one wheelchair accessible toilet compartment in all toilet rooms.

Can elements with knee and toe space overlap the required turning space?

Yes. Elements that provide compliant knee and toe space, such as lavatories, can overlap a portion of the turning space.

Can elements with knee and toe space overlap the door maneuvering clearance?
Door maneuvering clearance shown offset 8 inches maximum from the face of a door; a grab bar extends to a point near the latch side of the door and is within the 8 inch offset and does not overlap the door maneuvering clearance. Grab bars and other elements cannot overlap the door maneuvering clearance but can be located within the 8 inches maximum offset from the face of the door.

No. Elements, including those providing knee and toe space, cannot overlap or protrude into the maneuvering clearance required at doors and doorways. However, door maneuvering clearances can be offset up to 8″ from the face of the door to accommodate wall thickness, casework, shelves, or other elements adjacent to doorways, including grab bars. The door maneuvering clearance must be measured from the leading edge of such elements so that the full clearance is free of any obstruction.

Must toilet rooms be identified by the International Symbol of Accessibility (ISA)

Labeling accessible toilet rooms with the ISA is required only where inaccessible toilet rooms are present. For example, half of single user toilet rooms of the same type in each cluster (5% in the case of portable units) are required to comply, and those that are accessible must be identified by the ISA unless all are accessible (§213.2, Ex. 4, §216.8). In alterations where existing toilet rooms do not comply, directional signs with the ISA must be provided to indicate the location of the nearest accessible toilet room which must be labeled by the ISA.

Do the Standards require restroom pictograms?

No. The ISA is the only pictogram the Standards require in labeling toilet rooms. Other codes or regulations may require pictograms to identify men's and women's rooms and unisex restrooms. The Standards require that pictograms labeling permanent rooms and spaces, including toilet rooms, be on a field at least 6″ high and include the verbal equivalent in raised characters and braille below the pictogram. Informational pictograms, such as the ISA, are not subject to the requirements for field height or verbal text.

Do the Standards require accessible toilet compartments, including the ambulatory accessible compartment, to be labeled by the ISA?

No. The Standards do not require toilet compartments to be identified by the ISA.

Water Closets

Can an adjacent lavatory overlap the water closet clearance?

No. Lavatories are not permitted to overlap the 60″ wide minimum space at water closets, except in residential dwelling units if the water closet clearance is 66″ deep minimum (§604.3.2, Ex.). Lavatories (or other plumbing fixtures) can be adjacent to the water closet if recessed so as not to overlap the water closet clearance. (The rear grab bar can be 24″ long in this instance if there is not sufficient wall space for a 36″ grab bar.)

Can other elements overlap the water closet clearance?

The only elements beside the water closet that can overlap the water closet clearance are: associated grab bars, dispensers, coat hooks, shelves, and sanitary napkin disposal units (§604.3.2). No other elements can overlap the water closet clearance.

Can the toilet paper dispenser be mounted above the side grab bar?

Toilet paper dispensers can be mounted above the side grab bar if they do not protrude into the 12 inches high minimum clearance above the bar and the outlet is within the maximum 48 inches height. With large roll dispensers, ensuring that the outlet is within the height limit can be difficult when mounted above bars unless they are recessed.

How is the distance from the water closet measured for toilet paper dispensers with large or multiple rolls?

The required distance of toilet paper dispensers from the front of the water closet (7″ to 9″) is measured to the centerline of the dispenser, including large-roll and multiple-roll dispensers.

How can conflicts between the rear grab bar and the required location of flush controls be resolved?

If plumbing codes require a flush control location that conflicts with the rear grab bar, the grab bar may be split or shifted to the open side. This is permitted only where applicable codes mandate flush controls in such a location.

Are automatic (motion sensor) flush controls required to be on the open side of the water closet?

No. Motion activated flush controls are not required to be on the open side of the water closet. If a water closet has a manual flush control in addition to a motion activated one, it is recommended, but not required, that the manual control be located on the open side of the water closet. Manual flush controls, even those intended for custodian use, are helpful at water closets and urinals when the motion sensor fails to activate.

Are flush controls located on valves, walls, or tanks that are centered on the fixture compliant (i.e., on the open side)?

Manual flush controls, including push buttons, must be usable from a point between the centerline and the open side of the fixture. A portion of the control can be outside the range if it is usable without having to reach beyond the water closet centerline from the open side.

Can the side and rear grab bars be continuous?

Yes. The rear and side grab bar can be continuous or separate, but in either case must comply with the specified length and placement.

Must the side and rear grab bar both be at the same height within the specified 33″ to 36″ range?

The Standards do not require both grab bars at the water closet to be at the same height, although this is advisable. (Horizontal grab bars at showers must be at the same height.)

Can the side grab bar be located on a half wall or wing wall?

Grab bars, if properly secured, can be mounted on a half wall or wing wall where sufficient wall surface above the grab bar is available. Wall surface above grab bars provides support and helps prevent arms from slipping off the bar. Wall surface that extends the full height of the required 12″ clearance above grab bars, or preferably to the standard adult shoulder height for standees, should provide sufficient support in using grab bars.

Can the side grab bar be mounted on blocking when the centerline of the water closet exceeds the 18″ maximum?

In new construction, the wall should be furred out so that the water closet centerline is within the required 16″ to 18″ distance from the side wall. In addressing access to existing water closets that are too far from the side wall, the side grab bar can be mounted on blocking but it is important that the blocking extend at least 12″ above the grab bar so that adequate wall support is available when using the grab bar.

Can grab bar attachments be located at points along the bar instead of at the ends?

Yes. Grab bar attachments can be at points other than the ends of grab bars.

How is the length of grab bars measured?

Grab bar length is measured to the centerline of the return, consistent with industry convention. This also applies to post-mounted grab bars. When attached at points other than the ends (e.g., “European” style grab bars), the length is measured to the end of the bar.

Can grab bars be mounted to the floor instead of the wall?

No. The Standards require grab bars at water closets on the side and rear wall (§604.5). Grab bars that are floor-mounted obstruct usable clear floor space at the water closet and may be difficult to secure.

Must grab bars have a peened or other textured surface?

No. The Standards do not require grab bars to have peened or textured surfaces.

Are folding or swing-away grab bars permitted on the open side of water closets?

Folding or swing-away grab bars are not prohibited by the Standards so long as they do not obstruct use of the required grab bars. It is important that they are properly secured.

Is a vertical grab bar required by the Standards?

No. The ADA Standards do not require a vertical grab bar at water closets. However, the ICC A117.1 standard, which is referenced by the International Building Code, requires an 18″ minimum vertical grab bar on the side wall above the horizontal grab bar for people who are ambulatory. This grab bar can be located within the 12″ minimum clearance required above the horizontal grab bar.

Can grab bars have infill plates to prevent suicide or security risks in detention and correctional facilities?

In detention and correctional facilities, grab bars must fully comply at water closets serving accessible cells. Infill plates and other anti-ligature measures may be provided in detention and correctional facilities and other facilities so long as they do not impede gripping surfaces. Grab bars are not required in those cells that are specially designed without protrusions for suicide prevention (§604.5, Ex. 3).

Toilet Compartments

What distinguishes “toilet compartments” from single-user “toilet rooms”?

In some cases, it may be unclear whether water closets enclosed by full height partitions are to be treated as toilet compartments or single-user toilet rooms under the Standards. Toilet compartments can have full-height partitions. The determination typically is based on whether the toilet compartment is located within a restroom/ bathing facility or if it is entered directly from a common use corridor or exterior route. Those located within a room (such as a men's room, women's room, or gender neutral multi-user restroom, locker room, shower room) can be scoped as toilet compartments under the Standards: at least one wheelchair accessible and, if six or more water closets/urinals are provided, at least one ambulatory accessible compartment (§213.3.1). Those that directly connect to, or are separated by, a hallway, corridor, or exterior route, are scoped as single-user toilet rooms: all must comply except that where clustered, 50% of each use must comply (§213.2). If a toilet compartment contains more than one plumbing fixture (e.g., a lavatory), it must comply as a toilet room (§604.8).

Can compartment door openings be located more than 4″ from the side partition when the compartment width exceeds the 60″ minimum?

The Standards require the door opening to be located 4″ maximum from the side partition further from the water closet (or, if located in the side partition, 4″ maximum from the front partition). An increase above the 4″ maximum where compartments exceed the 60″ minimum width may not impact usability if the extra width of the compartment equals or exceeds the increase above the 4″ maximum (as permitted by the ICC A117.1 Standard), but such a departure must be based on the provision of equivalent facilitation (§103).

Are toilet compartment doors prohibited from swinging into fixture clearances?

Yes. Toilet compartment doors, including those of inaccessible compartments, cannot swing into clearances required at lavatories and other plumbing fixtures. In addition, the compartment doors cannot swing into the minimum required area of wheelchair accessible and ambulatory accessible compartments.

Are spring hinges and gravity hinges on compartment doors considered “closers” in determining the size of maneuvering clearances?

No. Some approaches require additional maneuvering clearance when a door or gate is equipped with a closer because of the additional force that must be counteracted in proceeding through doors. Since spring and gravity hinges do not significantly impact maneuvering at doors, they are not "closers" for purposes of specifying door maneuvering clearance.

Can accessible toilet compartments have full-height walls instead of partition panels?

Yes. But the minimum compartment size (both width and depth) is increased more than 6″ if minimum toe clearance is not provided below the front partition and a side partition. Doors, including full door assemblies, must be self-closing and meet all applicable requirements for doors.

Can pilasters or other partition supports intrude into the required toe clearance below partitions?

Yes. Vertical supports for partitions are permitted within the required toe clearance. The width of supports is not specified or limited by the Standards.

Lavatories and Mirrors

Can a lavatory be located outside of a toilet room?

The Standards do not prohibit location of lavatories outside toilet rooms where permitted by codes and other regulations.

Can a lavatory be provided in a wheelchair accessible toilet compartment?

Yes. But the toilet compartment must meet requirements for toilet rooms, including turning space (§604.8). A second accessible lavatory must be provided outside the compartment (§213.3.4).

Must the clear floor space at lavatories be centered?

It is advisable, though not required, that the clear floor space be nominally centered on the fixture.

Can accessible mirrors be located above lavatories?

Accessible mirrors can be located above lavatories or countertops if the bottom of the reflecting surface is 40″ maximum above the finish floor (§603.3). The bottom of the reflecting surface of mirrors not located above lavatories or countertops must be 35″ maximum above the finish floor.

If a toilet room has a full-length mirror and a mirror above a countertop or lavatory, must both types comply?

No. The Standards require only one mirror in a toilet room to comply. If mirrors are provided above lavatories or counters and at other locations in a toilet room, it is advisable, but not required, that one of each type comply.